7400 FAULT RECORDINGS
7402 INITIATION Initiation of data storage
STORAGE BY FD. [ ] Storage by fault det
STORAGE BY TRIP [ ] Storage by trip
START WITH TRIP [ ] Start with trip
7403 SCOPE Scope of stored data
FAULT EVENT [ ] Fault event
FAULT IN POW.SYS [ ] Fault in power syst.
7410 T-MAX Maximum time period of a fault recording
min. 0.30 s
max. 5.00 ©©©©
7411 T-PRE Pre-trigger time for fault recording
min. 0.05 s
max. 0.50 ©©©©
7412 T-POST Post-fault time for fault recording
min. 0.05 s
max. 0.50 ©©©©
7431 T-BINARY IN Storage time by initiation via binary input
min. 0.10 s
max. 5.00/Ñ ©©©©
7432 T-KEYBOARD Storage time by initiation via keyboard
min. 0.10 s
max. 5.00 ©©©©
7490 SYS LENGTH Length of fault record (former LSA)
660 VALUES FIX [ ] 660 values fix
<=3000 VAL. VAR [ ] <=3000 val. var
©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©
7800 SCOPE OF FUNCTIONS
7812 CHARAC. PH Characteristic O/C protection phases
DEFINITE TIME [ ] Definite time
INVERSE TIME [ ] Inverse time
7815 CHARAC. E Characteristic O/C protection earth
DEFINITE TIME [ ] Definite time
INVERSE TIME [ ] Inverse time
7827 THERMAL OL Thermal overload protection
NON-EXIST [ ] Non-existent
EXIST [ ] Existent
7833 INTERMIT.EF Intermittent earth fault protection
NON-EXIST [ ] Non-existent
EXIST [ ] Existent
7885 PARAM. C/O Parameter change-over
NON-EXIST [ ] Non-existent
EXIST [ ] Existent
7899 FREQUENCY Rated system frequency
fN50Hz []fN50Hz
fN60Hz []fN60Hz