1600 TRANSFORM. DIFF-PROT. DATA
1601 DIFF PROT. State of differential protection
OFF [ ] off
ON []on
BLOCK TRIP REL [ ] Block trip relay
1603 I-DIFF> Pick-up value of differential current
min. 0.15 I/InTr
max. 2.00 ©©©©
1604 I-DIFF>> Pick-up value of high set trip
min. 0.5 I/InTr
max. 20.0 ©©©©
1606 SLOPE 1 Slope 1 of tripping characteristic
min. 0.10
max. 0.50 ©©©©
1607 BASE PT 2 Base point 2 for slope 2 of tripping charact.
min. 0.0 I/InTr
max. 10.0 ©©©©
1608 SLOPE 2 Slope 2 of tripping characteristic
min. 0.25
max. 0.95 ©©©©
1610 2nd HARMON State of 2nd harmonic restraint
ON []on
OFF [ ] off
1611 2nd HARMON 2nd harmonic content in the different. current
min. 10 %
max. 80 ©©©©
1612 CROSSB 2HM Time for cross-blocking with 2nd harmonic
min. 0 *1P
max. 1000/Ñ ©©©©
1613 n. HARMON Choice of a further (n-th) harmonic restraint
5th HARMONIC [ ] 5th harmonic
4th HARMONIC [ ] 4th harmonic
3rd HARMONIC [ ] 3rd harmonic
OFF [ ] off
1614 n. HARMON n-th harmonic content in the differen. current
min. 10 %
max. 80 ©©©©
1615 CROSSB nHM Active time for cross-blocking with n-th harm.
min. 0 *1P
max. 1000/Ñ ©©©©
1616 IDIFFmax n Limit IDIFFmax of n-th harmonic restraint
min. 0.5 I/InTr
max. 20.0 ©©©©
1617 T-SAT-BLO. Max. blocking time at CT saturation
min. 2 *1P
max. 250/Ñ ©©©©