1618 SAT-RESTR. Min. restr. current for blocking at CT satur.
min. 5.00 I/InTr
max. 15.00 ©©©©
1625 T-DELAY > Trip time delay of diff. current stage IDIFF>
min. 0.00 s
max. 60.00/Ñ ©©©©
1626 T-DELAY >> Trip time delay of diff. current stage IDIFF>>
min. 0.00 s
max. 60.00/Ñ ©©©©
1627 T-RESET Reset delay after trip has been initiated
min. 0.00 s
max. 60.00 ©©©©
©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©
1700 GEN/MOTOR DIFF-PROTECTION
1701 DIFF PROT. State of differential protection
OFF [ ] off
ON []on
BLOCK TRIP REL [ ] Block trip relay
1703 I-DIFF> Pick-up value of differential current
min. 0.05 I/InGe
max. 2.00 ©©©©
1706 SLOPE 1 Slope 1 of tripping characteristic
min. 0.10
max. 0.50 ©©©©
1707 BASE PT 2 Base point 2 for slope 2 of tripping charact.
min. 0.0 I/InGe
max. 10.0 ©©©©
1708 SLOPE 2 Slope 2 of tripping characteristic
min. 0.25
max. 0.95 ©©©©
1717 T-SAT-BLO. Max. blocking time at CT saturation
min. 2 *1P
max. 250/Ñ ©©©©
1718 SAT-RESTR. Min. restr. current for blocking at CT satur.
min. 5.00 I/InGe
max. 15.00 ©©©©
1725 T-DELAY Trip time delay of differential protection
min. 0.00 s
max. 60.00/Ñ ©©©©
1727 T-RESET Reset delay after trip has been initiated
min. 0.00 s
max. 60.00 ©©©©