1800 BRANCH PT. DIFF-PROTECTION
1801 DIFF PROT. State of differential protection
OFF [ ] off
ON []on
BLOCK TRIP REL [ ] Block trip relay
1803 I-DIFF> Pick-up value of differential current
min. 0.30 I/InPt
max. 2.50 ©©©©
1806 SLOPE 1 Slope 1 of tripping characteristic
min. 0.10
max. 0.50 ©©©©
1807 BASE PT 2 Base point 2 for slope 2 of tripping charact.
min. 0.0 I/InPt
max. 10.0 ©©©©
1808 SLOPE 2 Slope 2 of tripping characteristic
min. 0.25
max. 0.95 ©©©©
1817 T-SAT-BLO. Max. blocking time at CT saturation
min. 2 *1P
max. 250/Ñ ©©©©
1818 SAT-RESTR. Min. restr. current for blocking at CT satur.
min. 5.00 I/InPt
max. 15.00 ©©©©
1825 T-DELAY Trip time delay of differential protection
min. 0.00 s
max. 60.00/Ñ ©©©©
1827 T-RESET Reset delay after trip has been initiated
min. 0.00 s
max. 60.00 ©©©©
1831 I DIFF>MON Pick-up value of diff. current monitoring
min. 0.15 I/InPt
max. 0.80 ©©©©
1832 T-MONITOR Time delay of blocking by monitoring
min. 1 s
max. 10/Ñ ©©©©
©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©
1900 REST.EARTH FAULT PROTECTION
1901 RESTR. E/F State of restricted earth fault protection
OFF [ ] off
ON []on
BLOCK TRIP REL [ ] Block trip relay
1903 I-REF> Pick-up value I REF> of restricted earth fault
min. 0.05 I/In
max. 2.00 ©©©©