1904 CRIT.ANGLE Critical angle of charact. trip-curve by REF
110 Ý [ ] 110 Ý
90 Ý []9
10 []10
120 Ý [ ] 120 Ý
130 Ý [ ] 130 Ý
1910 2nd HARMON State of 2nd harmonic restraint
OFF [ ] off
ON []on
1911 2nd HARMON 2nd harmonic contend in the REF-current
min. 10 %
max. 80 ©©©©
1912 I REFmax 2 Limit IREFmax of 2nd harmonic restraint
min. 1.0 I/In
max. 20.0 ©©©©
1925 T-DELAY Trip time delay of restricted earth fault
min. 0.00 s
max. 60.00/Ñ ©©©©
1927 T-RESET Reset delay after trip has been initiated
min. 0.00 s
max. 60.00 ©©©©
©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©
2100 BACK-UP OVERCURRENT TIME
2101 BACKUP O/C State of back-up overcurrent protection
OFF [ ] off
ON []on
BLOCK TRIP REL [ ] Block trip relay
2103 I>> Pick-up value for high current stage I>>
min. 0.10 I/In
max. 30.00 ©©©©
2104 T-I>> Delay time for I>> (definite time)
min. 0.00 s
max. 32.00/Ñ ©©©©
2111 CHARACT Overcurrent time stage characteristic
DEFINITE TIME [ ] Definite time
NORMAL INVERSE [ ] Normal inverse
VERY INVERSE [ ] Very inverse
EXTREMELY INVERS [ ] Extremely inverse
2112 I> Pick-up value of overcurrent time stage I>
min. 0.10 I/In
max. 30.00 ©©©©
2113 T-I> Delay time for I> (definite time)
min. 0.00 s
max. 32.00/Ñ ©©©©
2114 Ip Pick-up value of overcurrent time stage Ip
min. 0.10 I/In
max. 20.00 ©©©©