2115 T-Ip Time multiplier for Ip (inverse time)
min. 0.50 s
max. 32.00/Ñ ©©©©
2116 RMS FORMAT Method of RMS calculation for IDMT
WITHOUT HARMON. [ ] Without harmonics
WITH HARMONICS [ ] With harmonics
2118 T-RESET Reset delay after trip has been initiated
min. 0.00 s
max. 60.00 ©©©©
2121 MAN.CLOSE Effective stage after manual closing of CB
INEFFECTIVE [ ] Ineffective
I>> UNDELAYED [ ] I>> undelayed
I>/Ip UNDELAYED [ ] I>/Ip undelayed
©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©
2400 THERMAL OVERLOAD PROT. 1
2401 THERMAL OL State of thermal overload protection 1
OFF [ ] off
ON []on
BLOCK TRIP REL [ ] Block trip relay
ALARM ONLY [ ] Alarm only
2402 K-FACTOR K-factor for thermal overload protection 1
min. 0.10
max. 4.00 ©©©©
2403 T-CONSTANT Time constant for thermal overload protection1
min. 1.0 min
max. 999.9 ©©©©
2404 Î WARN Thermal warning stage
min. 50 %
max. 100 ©©©©
2405 I WARN Current warning stage
min. 0.10 I/In
max. 4.00 ©©©©
2406 O/L CALCUL Calculation method for thermal stages
Î MAX [ ] max. value of temperature rises of the phases
Î MEAN [ ] mean value of temperature rises of the phases
Î FROM IMAX [ ] temperature rise from max. current
©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©
2500 THERMAL OVERLOAD PROT. 2
2501 THERMAL OL State of thermal overload protection 2
OFF [ ] off
ON []on
BLOCK TRIP REL [ ] Block trip relay
ALARM ONLY [ ] Alarm only
2502 K-FACTOR K-factor for thermal overload protection 2
min. 0.10
max. 4.00 ©©©©