Technical Data (cont´d)
Warning!
If UV flame detectors QRA2 / QRA4 / QRA10 are used for flame supervision with
the LMV36, it must be ensured that the LMV36 is permanently connected to
power (conforming to DIN EN 298), thus enabling the LMV36 to detect flame
detector failures during startup and shutdown. Generally, the system works
with QRA flame detectors in intermittent operation. Technical Data refer to
Data Sheet N7712 covering UV flame detectors QRA2 / QRA10! Technical Data
refer to Data Sheet N7711 covering UV flame detectors QRA4
Required detector current in operation Min. 30 µA
When the more sensitive flame
supervision is activated, the required
detector current is halved (refer to chapter
Flame detection sensitivity in the Basic
Possible detector current in operati
Permissible length of flame detector
cable, normal cable (laid separately)
Max. 6 m
Threshold values when flame is supervised by QRA
Start prevention (extraneous light)
Flame intensity (parameter 954)
Legend
A Incidence of light
C Electrolytic capacitor 100...470 µF; DC 10...25 V
M Microammeter Ri max. 5000
Warning!
Input QRA... is not short-circuit-proof!
Short-circuits of X10-06 pin 2 against earth can destroy the QRA input
Simultaneous operation of QRA
and ionization probe is n
Flame supervision with
Measuring circuit for
detector current