FC1008/12-A/ -B/ -C
Fire control unit
Technical specification

Table of Contents

Questions and Answers

  • J
    jessicabushAug 16, 2025
    How to troubleshoot fire controls fault LED 14 flashing fast on Siemens Control Unit?
    • M
      Mark ObrienAug 16, 2025
      A rapidly flashing fire controls fault LED 14 on your Siemens Control Unit suggests a fault on a monitored control line, specifically one programmed in step 5 to option 12 or 13. Check the line for a short circuit, break, or a missing/defective EOL.
  • K
    kreedAug 19, 2025
    What to check if fault LED 2 is flashing fast on Siemens Control Unit?
    • J
      Jason ReynoldsAug 19, 2025
      Check if there is another fault LED flashing. If not, check if control input Fault is activated.
  • S
    Sara YorkAug 22, 2025
    Why is the power fault LED 11 flashing on my Siemens Control Unit?
    • B
      Brenda FlynnAug 22, 2025
      The LED 11 power fault on your Siemens Control Unit flashes for two primary reasons: either the battery is disconnected or low, or the mains supply is missing after the delay has expired. To resolve this, first, replace the battery. If the issue persists, check the internal fuse or the external mains breaker.
  • D
    Doris AnthonyAug 25, 2025
    How to fix the yellow zone LED flashing fast on Siemens Control Unit?
    • C
      Charles FuentesAug 26, 2025
      A rapidly flashing yellow zone LED on your Siemens Control Unit indicates a fault in zone number x. You should check if any detector head is removed and inspect the line for a short circuit, break, or a missing/defective EOL.
  • D
    Dr. Joseph MendozaAug 28, 2025
    What to do if the alarm horn fault LED 13 is flashing fast on Siemens FC1008-A?
    • P
      Peggy BurkeAug 28, 2025
      If the alarm horn fault LED 13 is flashing rapidly on your Siemens Control Unit, it signifies a fault in the monitored control lines (horn). Inspect the lines for a short circuit, break, or a missing/defective EOL. If a control card FCA1003 is in use, check LEDs DL1 - DL4 to identify the faulty line.
  • B
    Brett SweeneyAug 31, 2025
    What does it mean when LED 10 earth fault is flashing fast on Siemens Control Unit?
    • C
      Cynthia HendersonAug 31, 2025
      A rapidly flashing LED 10 for earth fault on your Siemens Control Unit indicates that some part of the system has a leakage to earth. Remove external lines (detector line etc.) one by one until the fault disappears, and then repair the defective line. If no external line has a leakage to earth, consider replacing the mainboard.
  • V
    victor68Sep 3, 2025
    Why is the RT-Fault LED 15 flashing fast on my Siemens FC1008-A Control Unit?
    • E
      erin46Sep 3, 2025
      The rapid flashing of the RT-Fault LED 15 on your Siemens Control Unit can occur because the control input Fault RT is active, or if a programmable control input with option 1 is active indicating a fault with the remote transmission device. Check the remote transmission device. It can also mean there is a fault on a monitored control line (programmed in step 5 to option 14), so check the line for a short circuit, break, or missing/defective EOL.
  • A
    Andrew SellersSep 6, 2025
    What should I do if the system fault LED 12 is flashing fast on my Siemens FC1008-A?
    • J
      Jessica BraunSep 6, 2025
      If the system fault LED 12 is flashing rapidly on your Siemens Control Unit, it indicates that the microcomputer has failed and the system is not working. Try switching the power off and restarting the system. If the fault persists, replace the mainboard.
  • J
    Jessica PerezSep 9, 2025
    What does it mean when the RT-Alarm LED 23 is flashing fast on Siemens FC1008-A?
    • D
      Danielle JeffersonSep 9, 2025
      A rapidly flashing RT-Alarm LED 23 on your Siemens Control Unit indicates a fault on a monitored control line, specifically one programmed in step 5 to option 11. Check the line for a short circuit, break, or a missing/defective EOL.
  • L
    Lisa DunnSep 12, 2025
    Why does my Siemens FC1008-A display 88.88?
    • D
      Deanna McculloughSep 12, 2025
      The Siemens Control Unit displaying 88.88 indicates that the clock has not been set, which typically occurs with a new system startup or after a power down. Set the date and time to resolve this.

Summary

Installation

Function and Design

Mainboard Hardware Settings

Explains the function and configuration of mainboard hardware settings (jumpers).

Event Processing

Illustrates the processing logic for alarm and fault events within the system.

Operation and Indicator Elements

Commissioning

Procedure

Outlines the steps for commissioning the system, including hardware checks and function tests.

Configuration

Programming User Functions

Guides on adjusting programmable user functions via single programming steps.

Programming Steps

Explains how to select and set programming steps for the unit.

Programmable Functions

Maintenance

Trouble Shooting

Interpretation of Fault LED Flashing

Explains fault causes and actions based on LED flashing patterns.

Siemens FC1008-A Specifications

General IconGeneral
ModelFC1008-A
ManufacturerSiemens
Number of Loops1
RedundancyNo
DisplayLCD
Power Supply24 V DC
Protection ClassIP30
TypeFire Alarm Control Panel