EasyManua.ls Logo

Siemens FC1008-A - Control Line Extension Card

Siemens FC1008-A
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Function and design
18
Building Technologies A6V10265083_a_en_--
Fire Safety & Security Products 03.2010
5.1.6 Control line extension card
Summery
The optional control line extension card features 4 monitored control outputs (con-
trol line 3 - 6). The following devices can be connected to the control outputs:
Alarm devices like horns or flashlights
Remote fire control installations
RT devices
Functionality
The control outputs of control lines 3 – 6 have basically the same features as the
control outputs of control lines 1 and 2. For the control lines 3 - 6, attention should
be paid to the following:
It is defined in programming step 5 when and how the control outputs are acti-
vated. In addition, each control output (control line 3 – 6) has a control
input (A – D). Input A is related with output 3 etc. An AND combination between
the setting in programming step 5 and the control input is enabled with a
Jumper, e.g. control output 3 shall only be activated in case of alarm 2 AND
driver output of zone 4 is active.
Only control line 6 can be activated in case of a RT fault (see Step 5, activation
mode of control lines, option 14). If so, the Jumpers have to be set accordingly
(see table below).
A LED is assigned to each control output. If the LED flashes, the corresponding
control output has either a line break or a short line.
Connection
The board will be connected via the enclosed ribbon cable on the connector
CN10 to the main board.
For power supply, a separate line has to run from the power supply card (termi-
nals on the right side of the card) to the control line extension card.
If a control line is not used, it to has to be terminated with an EOL (FCE1002; in-
cluded in delivery).
The allocation of connection can be seen in the following board illustration.
Ref. Control
line
Setting / Function
PU1,
PU2
6
Pos. top = if option 14 progr. step 5 is selected
Pos. bottom = if option 1-13 in progr. step 5 is selected
PU3 5
PU4 6
PU5 4
PU6 3
OFF = zone-specific activation (control input used)
ON = common activation (control input not used)
DL1 3 LED flashing upon break or short
DL2 4 LED flashing upon break or short
DL3 5 LED flashing upon break or short
DL4 6 LED flashing upon break or short
CN1 Connector for flat cable to main board
F1 3 500 mAT Control line 3
F2 4 500 mAT Control line 4
F3 5 500 mAT Control line 5
F4 6 500 mAT Control line 6
PU4
PU3
PU5
PU6
PU2
PU1
DL1
DL2
DL3
DL4
A
B
C
D
+
-
+
-
+
-
+
-
+
-
CN1
1N4007
3
6
control input for line 6
control input for line 5
control input for line 4
control input for line 3
For zone-specific
activation only
input 24V supply
5
4
6
A
top
F1
F3
F4 F2
(A) Special Application: Line 6 used as remote control of state RT-fault
- Function: Line is activated in normal operating state and inactive in state system fault and on power off (FC10)
- Only possible with line 6
- Program option 14 in programming step 5
- Set jumper PU1 and PU2 on FCA1003 to position top
- Connect load between 350 … 2500 (without EOL)

Table of Contents

Related product manuals