Operator Interface Guide
Document No. 125-703
September 19, 2017
Room Unit for TEC, and ATEC
Page 1 of 4
Overview
This document explains the set up and operation of the
Series 2200, and 3200 room units. It explains the
various operating modes available and describes the
procedure for programming the display, according to
user preferences.
These devices are used with BACnet Terminal
Equipment Controllers (TEC), BACnet Actuator TEC
(ATEC) Controllers, and BACnet Programmable
Controllers (PTEC).
Product Numbers
QAA2280.FWNC QPA228x.FWSC
QAA2280.FWSC QFA3280.FWNC
QPA228x.FWNC QFA3280.FWSC
Accessories
Description Product Number
Passkey 544-643A
25-foot (7.6 m) cable with
connections
588-100A
50-foot (15.2 m) cable with
connections
588-100B
100-foot (30.5 m) cable with
connections
588-100C
Replacement Relative
Humidity Sensing Element
for QFA and QPA
AQF3060
Replacement Housing Base
(QAA, QFA types)
563-102-01
Replacement Housing Base
(QPA types)
563-120
Room Unit Backplate,
10-pack
AQM2200-INTL
Power Supply (QPA types)
AQM2200
Wall Gasket, 10-pack
563-102 GSKT KIT
Operation
Operation modes
Figure 1. Operation Modes.
Normal Mode
In Normal Mode, the display is updated with
temperature, humidity, carbon dioxide, and/or occupied
status (all where applicable) on a set time cycle.
The display shows temperature in the desired units (as
set by the clipable jumper on the PCA). Depending on
the model, the humidity and/or carbon dioxide value(s)
will be displayed as well. When multiple variables need
to be displayed (temperature, relative humidity, and/or
carbon dioxide) the display will cycle through the
required values at a rate of one change every three to
five seconds.
Question and Answer IconNeed help?

Do you have a question about the Siemens QPA228.FWNC Series and is the answer not in the manual?

Siemens QPA228.FWNC Series Specifications

General IconGeneral
BrandSiemens
ModelQPA228.FWNC Series
CategoryControl Unit
LanguageEnglish

Summary

Overview of Room Units

Operation and Modes

Operation Modes

Describes the different operating modes available for the room unit.

Normal Mode Operation

Details how the display updates and shows values in Normal Mode.

Occupied Mode Control

Explains how to switch between occupied and unoccupied modes.

Setpoint Adjustment Mode

Describes how to adjust the temperature setpoint using buttons.

Passkey Mode Usage

Explains how to use the passkey for user functionality and settings.

User Settings Configuration

Setpoint Display Settings

Determines how the temperature setpoint is displayed (numeric or graphic).

Setpoint Range Limits

Sets the minimum and maximum temperature setpoint values.

Display Variable Settings

Controls display of temperature, humidity, CO2, and occupancy status.

Field Calibration

Allows field calibration of temperature, humidity, and CO2 values.

Display Brightness and Screen Saver

Adjusts display brightness and enables screen saver functionality.

Factory Defaults Reset

Resets all parameters to factory defaults.

Laptop Pass-thru Mode

Error Message Reference

NO TEC Communication Error

Indicates no communication with the TEC.

NO SENSOR Detection Error

Indicates no temperature, humidity, or CO2 sensor detected.

Firmware Revision/Error Codes

Indicates room unit firmware revision or specific error codes.

Temperature Unit Conversion

Related product manuals