146/221 
Siemens Switzerland Ltd 
User manual RVS61.843 CE1U2355en_02 
HVAC Products  6 The settings in detail  23. November 2007 
Collector pump 2 Q16 
For control of the circulating pump of a second solar collector circuit.  
 
Solar pump ext exch K9 
For the external heat exchanger, solar pump “Ext heat exchanger K9“ must be set at 
the multifunctional relay output (QX). 
If both a DHW and a buffer storage tank are available, operating line 5841 “External 
solar exchanger“ must also be set.  
 
Solar ctrl elem buffer K8 
If several heat exchangers are used, the buffer storage tank must be set at the 
respective relay output and, in addition, the type of solar controlling element must be 
defined on operating line 5840).  
 
Solar ctrl elem swi pool K18 
If several heat exchangers are used, the swimming pool must be set at the respective 
relay output and, in addition, the type of solar controlling element must be defined on 
operating line 5840).  
 
El imm heater buffer K16 
The relay is used for the control of an electric immersion heater in the buffer storage 
tank.  
Important! 
Electric immersion heaters must be fitted with a safety limit thermostat. 
 
H1 pump  Q15 
Pump H1 can be used for an additional consumer. Together with an external request 
for heating / cooling at input H1, the application is suited for an air heating coil / air 
cooling coil, for instance. The pump’s overrun time is always 1 minute.  
 
H2 pump Q18 
Pump H1 can be used for an additional consumer. Together with an external request 
for heating / cooling at input H2, the application is suited for an air heating coil / air 
cooling coil, for instance. The pump’s overrun time is always 1 minute. 
 
H3 pump Q19 
Pump H1 can be used for an additional consumer. Together with an external request 
for heating / cooling at input H3, the application is suited for an air heating coil / air 
cooling coil, for instance. The pump’s overrun time is always 1 minute.  
 
Heat circ pump HCP Q20 
The relay is used for the control of heating circuit pump Q20. 
 
2. Pump speed HC1 Q21 / HC2 Q22 / HCP Q23 
This function facilitates the control of a 2-speed heating circuit pump, allowing the 
pump’s capacity to be lowered in Reduced mode (e.g. during night setback). In that 
case, after pump speed 1, pump speed 2 is switched on as follows via “Multifunctional 
relay RX“: