Minimum flow temp setpoint 
Consumers requiring a minimum flow temperature can request it via contact Hx (e.g. air 
heating coil for air curtain). 
When the contact closes, the temperature setpoint adjusted on operating line 5952 / 
5962 is demanded. 
 
Heat request 10V 
Heat generation receives heat requests in the form of voltage signals (DC 0...10 V). 
The associated setpoint is calculated on the basis of the straight line defined with 
operating lines 5952 – 5956 (for H1), or 5962 – 5966 (for H3).
 
 
Dewpoint monitor 
To detect the formation of condensation in the cooling circuit, a dewpoint monitor can 
be connected to input Hx.  
If the dewpoint monitor trips, the cooling circuit is immediately switched off. 
The cooling is enabled again when the dewpoint monitor reverts to normal and an 
adjustable locking time (946) has elapsed. 
 
Flow temp setp inc hygro 
To prevent the formation of condensation due to high indoor air humidity, a hygrostat 
can be connected to input Hx.  
If the hygrostat trips, the flow temperature setpoint is increased by the fixed value of 
"Flow temp setp incr hygro" (947). As soon as the hygrostat reverts to normal, the flow 
temperature setpoint returns to the "normal value". 
 
Refrigeration request 
If the connected contact closes, the controller drives the heat pump to the fixed 
temperature setpoint adjusted on operating line 5952 (for H1), 6048 (for H2), or 5962 
(for H3). If the refrigeration request made is lower, consideration is given to it. 
 
Refrig request 10V 
Refrigeration generation receives the refrigeration request in the form of voltage signals 
(DC 0...10 V). 
The respective setpoint in °C is determined via the linear characteristic which is defined 
by 2 fixed points (voltage value 1 / function value 1, and voltage value 2 / function value 
2). 
 
Pressure measurement 10V 
The controller receives the pressure signal in the form of voltage signals (DC 0...10 V). 
The respective pressure value is calculated via the linear characteristic which is defined 
by 2 fixed points (voltage value 1 / function value 1 and voltage value 2 / function value 
2). 
If the pressure value crosses one of the set limit values, an error or maintenance 
message is delivered. If the value falls below the critical pressure limit, the heat pump is 
shut down. 
The values of the maximum, minimum and critical water pressure for H1 can be set 
under 6140 OEM...6142 OEM, foür H2 under 6150 OEM…6152 OEM, and for H3 
under 6180 OEM…6182 OEM  
 
Rel room humidity 10V 
The controller receives the relative humidity signal in the form of voltage signals (DC 
0...10 V). 
The respective room humidity is calculated via the linear characteristic which is defined 
by 2 fixed points (voltage value 1 / function value 1 and voltage value 2 / function value 
2).