pump is shut down by a safety function (e.g. due to high-pressure, low-pressure, or hot-
gas temperature).  
Internal requests, DHW requests and requests via bus are suppressed. No 
consideration is given to minimum off time and minimum running time. The prerun and 
overrun times of the condenser pump and source pump are taken into account. Normal 
defrost is possible. 
 
NC contact 
The contact is normally closed and must be opened to activate the selected Hx 
function. 
NO contact 
The contact is normally open and must be closed to activate the selected function Hx. 
 
The descriptions given on the functions of contact Hx refer to the setting as NO contact. 
 
If input H1, H2, H3 (5950, 6046, 5960) is used as a contact input (”Min flow temp setp” 
or “Refrigeration request”), the controller uses the value set here as the setpoint. 
The heat pump is controlled constantly at the temperature level set here, either until 
contact Hx opens again or until a higher heating / cooling request is delivered.  
If several requests for heating or cooling are received at the same time (contact Hx, 
DHW or from the controller itself), the highest or lowest of them is automatically 
selected. 
 
Example of minimum flow temperature setpoint: 
30 20 10 0 -10
40
30
60
50
80
70
TVw
TVw
2355Z20
TA
°C
°C
gem
 0
TVHw
 
TVHw  Minimum flow temperature setpoint 
TVw  Flow temperature setpoint 
 
These settings can be made for each input Hx. 
The linear characteristic is defined via 2 fixed points. The setting is made with 2 
parameter pairs for 
Function value and Voltage value (F1/U1 and F2/U2). 
•  Example for heat or refrigeration request 10 V 
 
Type of contact Hx 
 
Function value contact Hx 
 
Voltage value 1 
Function value 1  
Voltage value 2 
Function value 2