CPUs
1-73
PLC S7-300, CPU Specifications CPU 312 IFM to CPU 318-2 DP
A5E00111190-01
DP Master
Services
Equidistance Yes
SYNC/FREEZE Yes
Activation/deactivat
ion of DP slaves
Yes
Transmission rates Up to 12 Mbps
Address area max. 2 KB I/2 KB O
User data per DP slave max. 244 bytes I and
244 bytes O
DP Slave
Services
Status/Modify;
Program; Routing
Yes, can be activated
Device master file siem807f.gsg
Transmission rate Up to 12 Mbps
Transfer memory 244 bytes I/244 bytes O
2. Interface
Functionality
DP Master Yes
DP Slave Yes
Status/Modify;
Program; Routing
Yes, can be activated
Direct data exchange Yes
PtP Connection No
Default setting None
Galvanically isolated Yes
Number of connections max. 16
Of these, the
following are
reserved:
1 PD connection
1 OP connection
DP Master
Services
PD/OP
communication
Yes
Equidistance Yes
SYNC/FREEZE Yes
Activation/deactivat
ion of DP slaves
Yes
Transmission rates Up to 12 Mbps
Number of DP slaves max. 125
Address area max. 8 KB I/8 KB O
User data per DP slave max. 244 bytes I and
244 bytes O
DP Slave
Services
Status/Modify;
Program;
Routing
GSD file
Transmission speed
Transfer memory
Yes, can be activated
siem807f.gsg
Up to 12 Mbps
244 bytes I/244 bytes O
Dimensions
Assembly dimension
BHT (mm)
160125130
Weight Approx. 0.93 kg
Programming
Programming language STEP 7
Stored instructions See Instruction List
Nesting levels 16
System functions (SFCs) See Instruction List
System function blocks
(SFBs)
See Instruction List
User program security Password protection
Voltages, Currents
Power supply 24V DC
Permissible range 20.4 V to 28.8 V
Current consumption (idle) typical 1.2 A
Inrush current typical 8A
l
2
t 0.4 A
2
s
External fusing for supply
lines (recommendation)
Circuit breaker; 2 A,
Type B or C
PD supply at MPI (15 to
30V DC)
max. 200 mA
Power losses typical 12 W
Battery Yes
Backup margin at 25
C and continuous CPU
buffering
min. 1 year
Battery shelf life at
25C
approx. 5 years
Accumulator Yes
Clock back-up period
at 0 to 25C Approx. 4 weeks
at 40 C Approx. 3 weeks
at 60 C Approx. 1 week
Battery charging time Approx. 1 hour