Technical data of CPU 31xC
6.3 CPU 313C
CPU 31xC and CPU 31x, Technical Data
6-10 Manual, 01/2006 Edition, A5E00105475-06
Technical data
Digital channels Max. 1016
Centralized
Max. 992
Integrated channels
24 DI / 16 DO
Analog channels Max. 253
Centralized
Max. 248
Integrated channels
4 + 1 AI / 2 AO
Removal
Module rack Max. 4
Modules per rack Max. 8; Max. 7 in rack 3
Number of DP masters
Integrated
None
Via CP
4
Operable function modules and communication
processors
FM
Max. 8
CP (PtP)
Max. 8
CP (LAN)
Max. 6
Time
Clock Yes (hardware clock)
Buffered
Yes
Buffered period
Typically 6 weeks (at an ambient temperature of
40 °C)
Behavior of the clock on expiration of the
buffered period
The clock keeps running, continuing at the time-
of-day it had when power was switched off.
Accuracy
Deviation per day < 10 s
Operating hours counter 1
Number
0
Value range
2
31
hours
(if SFC 101 is used)
Granularity
1 hour
Retentive
Yes; must be manually restarted after every
restart
Time synchronization Yes
In the PLC
Master
On MPI
Master/slave
S7 message functions
Number of stations that can be logged on for
signaling functions
Max. 8
(depends on the number of connections
configured for PG / OP and S7 basic
communication)
Process diagnostics messages Yes
Simultaneously enabled interrupt S blocks
Max. 20

Table of Contents

Other manuals for Siemens CPU 312C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CPU 312C and is the answer not in the manual?

Siemens CPU 312C Specifications

General IconGeneral
BrandSiemens
ModelCPU 312C
CategoryProcessor
LanguageEnglish

Related product manuals