Technical data of CPU 31xC   
6.5 CPU 314C-2 PtP and CPU 314C-2 DP 
  CPU 31xC and CPU 31x, Technical Data 
6-26  Manual, 01/2006 Edition, A5E00105475-06 
Technical data 
  CPU 314C-2 PtP  CPU 314C-2 DP 
•  Enable/disable DP slaves 
–   Yes 
•  DPV1 
–   Yes  
•  Transmission rates 
–   Up to 12 Mbaud 
•  Number of DP slaves per station 
–   Max. 32 
•  Address area 
–   Max. 1 KB I / 1 KB O 
•  User data per DP slave 
–   Max. 244 bytes I / 244 bytes O 
DP slave   
Number of connections  –   12 
Services     
•  PG/OP communication 
–   Yes 
•  Routing 
–   Yes (only if interface is active) 
•  Global data communication 
–   No 
•  S7 basic communication 
–   No 
•  S7 communication 
–   No 
•  Direct data exchange 
–   Yes 
•  Transmission rates 
–   Up to 12 Mbaud 
•  Intermediate memory 
–   244 bytes I / 244 bytes O 
•  Automatic baud rate search 
–   Yes (only if interface is passive) 
•  Address areas 
  Max. 32, with Max. 32 bytes each 
•  DPV1 
–   No  
GSD file  –   The latest GSD file is available at: 
http://www.automation.siemens.com/csi/
gsd  
Point-to-point connection 
•  Transmission rates 
38.4 Kbaud half duplex 
 19.2 Kbaud full duplex 
–  
•  Cable length 
Max. 1200 m  –  
•  User program can control the 
interface 
Yes  –  
•  The interface can trigger a break or 
an interrupt in the user program 
Yes (message with break ID)  –  
•  Protocol driver 
3964 (R); ASCII and RK512  –  
Programming  CPU 314C-2 PtP  CPU 314C-2 DP 
Programming language  LAD/FBD/STL 
Available instructions  see the Instruction List 
Nesting levels  8 
System functions (SFCs)  see the Instruction List 
System function blocks (SFBs)  see the Instruction List 
User program security  Yes