Installation Instructions
Document No. 129-906
July 20, 2016
Spanish Version
Item Number 129-906, Rev. EA Page 1 of 18
Para accede al documento en Español, escanee el código QR que se encuentra en la parte trasera del termostato.
Figure 1. 97-004 Thermostat.
Product Specifications
Conventional Up to 3 Heating/3 Cooling
Heat Pumps Up to 4 Heating/2 Cooling
Electrical Characteristics
Power Supply
24 Vac +/-20%, Class 2, 4A
max.
Power Usage 5 VA (maximum)
Output Relay
Ratings
Pilot duty, 1A max. per output,
4A max total
Operating
Temperature
23°F to 122°F (-5°C to 50°C)
Storage/Shipping
Temperature
-13°F to 158°F (-25°C to 70°C)
Relative
Humidity
Up to 95% (non-condensing)
Rating NEMA 1
NOTE: The 97-004 is not battery-powered. It requires
24 Vac power from the HVAC equipment at
terminals RH/RC and C.
Product Number
97-004
Product Information
The EcoView Thermostat (97-004) is a wireless,
digital thermostat, designed for use with the
EcoView Energy Management System.
See the following documents for installation of other
EcoView system components:
• EcoView™ 8 DO Module Installation and
Commissioning (129-565)
• EcoView™Multi-phase Meter Installation
Instructions (129-563)
• EcoView™ Touchscreen Installation and
System Start-up (129-562)
Caution Notations
Equipment damage or loss of data may
occur if you do not follow a procedure as
specified.
Risque de dégâts matériels ou de perte de
données, en cas de non-respect des
procédures à suivre.
Required Tools
• No. 1 Phillips screwdriver
• 1/8” flat-blade screwdriver
• Drill with 1/8" drill bit
Expected Installation Time
15 minutes
Prerequisites
• All work must be performed in accordance with
applicable codes and standards.
• Use 18 gauge thermostat wire for equipment
connections.
• 22 gauge shielded cable is recommended for
remote sensor wiring. Do not exceed 150 feet.
• To replace an existing thermostat, verify if 24
Vac is present between the RH/RC and C
terminals.