Intended use
The flame detector measures infrared radiation and can
therefore detect organic material fires with and without
smoke.
FDF221-9 can be used in indoor areas without deceptive
phenomena.
Thanks to extended sensory technology, FDF241-9 is not
susceptible to deceptive phenomena (e.g. the sun) and
can therefore also be used in outdoor areas.
Assembly
The installation process depends on the detector line type
(collective or FDnet/C-NET).
Setting parameter set (collective)
For collective operation, the parameter set is set via the
DIP switches in the flame detector.
1. Loosen screw (3) on rear of flame detector.
2. Open swiveling cover (1).
3. Use DIP switches (2) to set the parameter set you want
(see table below).
4. Close swiveling cover (1) and fix with screw (3).
Installing flame detector on base for flame detector
WARNING
Danger of falling
Bodily injury
When installing, use a secured ladder or work
platform.
WARNING
Falling flame detector
Bodily injury
Never leave the flame detector hanging with the
connection cable connected to the base for flame
detector.
1. Remove bridging connector (7) from base for flame
detector (4).
2. Use connection cable (6) to connect connections (8) in
base for flame detector (4) and on flame detector.
3. Use four screws (5) to secure flame detector to base
for flame detector (4).
Setting parameter set (FDnet/C-NET)
The parameter set is set using control panel. For this, use
the control panel documentation.
For more information, see documents
007011 (Technical manual) and
A6V10299652 (Commissioning).
Parameter set DIP switch
No. FDF221-9 FDF241-9 1 2 3 4 5 6
01 Robust Robust
on off off off off off
02 - Universal
off on off off off off
03 Universal fast Universal fast
on on off off off off
04 Sensitive Sensitive
off off on off off off
05 Sensitive fast Sensitive fast
on off on off off off
06 - Rapid
off on on off off off
07 - Motor test bed
on on on off off off