Siemens FDO221 - Specification; Parameter Sets: Heat Detector; Heat Detector FDT241; Description

Siemens FDO221
138 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3BPlanning
27BParameter sets: Heat detector
4
67 |
138
Building Technologies
007004_t_en_--
Fire Safety
2015-11-04
4.4.2.3 Specification
No.
Name
Response time [s]
Sensitivity [%/m]
2 Standard 60 2.8
3 Standard Plus 50 2
All parameter sets meet the criteria of standard EN 54-7.
4.5 Parameter sets: Heat detector
4.5.1 Heat detector FDT241
4.5.1.1 Description
The heat detector FDT241 has the following parameter sets:
A1R (1)
BR (2)
A1S (3)
BS (4)
Download 1 (14) / Download 2 (15)
Application-specific parameter sets that can be loaded on-site (depending on
the control panel).
Notes on the designations A1 and B
A1 parameter sets should be operated at a room temperature of around 25 °C.
However, they can be applied at temperatures up to 50 °C. The static response
temperature is 60 °C.
B parameter sets are normally operated at around 40 °C. They can however be
used at up to 65 °C. The static response temperature is 80 °C.
Notes on the designations R and S
Compared with S parameter sets, R parameter sets also trigger an alarm when the
temperature increases (e.g. from 20 °C to 50 °C within a few minutes).