4BMounting / Installation
38BBase attachment wet FDB295
5
81 |
138
Building Technologies
007004_t_en_--
Fire Safety
2015-11-04
5.8 Base attachment wet FDB295
The 'base attachment wet FDB295' is for surface-mounted feed lines in humid
and cold environments.
It is not possible to remove the detector using the detector tester
FDUD291/detector exchanger and tester FDUD292/intelligent detector tester
FDUD293.
The cables are inserted using M20 x 1.5 metal cable glands (Fig. 3).
Protective cages DBZ1194/FDBZ294 can be installed on 'base attachment wet
FDB295'.
Protective cage DBZ1194 (Fig. 3) protects the detector against mechanical
damage.
EMC-protective cage FDBZ294 (Fig. 4) protects the detector against
mechanical damage and electromagnetic fields.
Note the dimensions of the protective cages (Fig. 3).
To connect detector heating unit FDBH291, see chapter: 'Connection of the
detector heating unit [➙ 96]'.