4BMounting / Installation
49BDetector lines
5
102
| 138
007004_t_en_--
2015-11-04
5.19.2.1 Use of unshielded cables
The connection is established from base to base using twisted or non-twisted wire
pairs.
Connection diagram for collective detector line with and without external alarm indicators (without
shielded cables)
1
Control panel 3
External alarm indicator
2
Detector bases FDB201/FDB201-AA, FDB202 4
End-of-line depending on control panel
Standard circuitry
With standard circuitry, the external alarm indicator is connected to the positive and
negative poles of each detector.
Wire-saving cabling
NOTICE
No approval
Wire-saving cabling in external alarm indicators is prohibited for new sites
The base adapter FDB299 must be used for the FDOOT241-A9.
With wire-saving cabling, the external alarm indicator is connected as follows:
The external alarm indicator must be connected to the positive and negative
poles of at least one detector (A).
The external alarm indicator must be connected to the positive pole of every
other detector (B).
The external alarm indicator need not be connected to the negative pole of
every other detector (C).
+
-
+
-
+
-
+
-
+
-
+
-
LINE
+
-
+
-
+
-
+
-
1
2
C
4
B
3
A
+