EasyManua.ls Logo

Siemens FDT221 - Page 128

Siemens FDT221
138 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7BSpecifications
54BTechnical data FDOOT221, FDOOT241-x / -Ax
8
128
| 138
007004_t_en_--
2015-11-04
SIGMALOOP detector line (FDOOT241-A4)
Detector line
Operating voltage (modulated) DC 10…28 V
Operating current (quiescent) Typ. 200 µA
Maximum current connection factor 1
Address connection factor 1
Protocol SIGMALOOP
Compatibility See 'List of compatibility'
Line separator
Line voltage:
Nominal DC 24 V (= V
nom
)
Minimum DC 10 V (= V
min
)
Maximum DC 28 V (= V
max
)
Voltage at which the line separator opens:
Maximum DC 10 V (= V
SO max
V
min
)
Permanent current when switches are closed Max. 0.032 A (= I
C max
)
Switching current (e.g., in the event of a short-
circuit)
Max. 0.2 A (= I
S max
)
Leakage current when switches are open Max. 50 µA (= I
L max
)
Serial impedance when switches are closed Max. 0.8 Ω (= Z
C max
)
External alarm indicators
External alarm indicators which can be
connected
2
Voltage DC 8…17 V
Current 9…15 mA
Length of line Max. 10 m
Flashing interval times:
Bright 15 ms
Dark 1 s

Table of Contents