EasyManua.ls Logo

Siemens GMI Series - Overhaul Procedures; Circuit Breaker Overhaul Schedule; Component Replacement

Siemens GMI Series
46 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Maintenance
&
Overhaul
Page
26
Electrical
Control
Checks
The
electrical
controls
of
the
GMI
circuit
breaker
should
be
checked
during
annual
inspections
to
verify
absence
of
any
mechanical
damage
,
and
proper
operation
of
the
automatic
spring
charging
and
Close
and
Trip
circuits
.
Unless
otherwise
noted
,
all
of
these
tests
are
performed
without
any
control
power
applied
to
the
circuit
breaker
.
Check
of
the
Wiring
and
Terminals
1
.
Physically
check
all
of
the
breaker
wiring
for
evidence
of
abrasion
,
cuts
,
burning
or
mechanical
damage
.
2
.
Check
all
terminals
to
be
certain
they
are
solidly
attached
to
their
respective
device
.
Figure
48
shows
the
terminals
for
the
Close
solenoid
.
The
terminals
of
the
trip
solenoid
and
the
spring
charging
motor
are
similar
.
Figure
49
.
Secondary
Disconnect
Fingers
.
Automatic
Spring
Charging
Check
-
Control
Power
Required
Repeat
the
automatic
spring
charging
check
described
in
the
section
entitled
Installation
Checks
&
Initial
Functional
Tests
.
Primary
tasks
of
this
check
are
:
1
.
The
breaker
is
energized
with
control
power
for
this
check
.
2
.
De
-
energize
the
source
of
control
power
.
Figure
1
.
3
.
Install
the
breaker
end
of
the
split
plug
jumper
over
the
secondary
disconnect
of
the
circuit
breaker
.
The
split
plug
jumper
has
one
male
and
one
female
connector
and
cannot
be
installed
incorrectly
.
Figure
7
.
4
.
Install
the
switchgear
end
of
the
plug
jumper
over
the
secondary
disconnect
block
inside
the
switchgear
.
Figure
8
.
5
.
Energize
the
control
power
source
.
6
.
When
control
power
is
connected
to
the
circuit
breaker
,
the
closing
springs
should
automatically
charge
.
Visually
verify
that
the
closing
springs
are
charged
.
Figure
48
.
Terminals
for
Close
Solenoid
.
Check
of
the
Secondary
Disconnect
In
addition
to
checking
the
terminals
of
the
secondary
disconnect
,
the
contact
fingers
need
to
be
free
to
move
without
binding
.
Figure
49
shows
the
secondary
disconnect
fingers
.
Depress
each
finger
,
confirm
presence
of
spring
force
(
con
-
tact
pressure
)
,
and
verify
freedom
of
motion
.
(
Courtesy of NationalSwitchgear.com

Other manuals for Siemens GMI Series

Related product manuals