Interrupter
/
Operator
Description
Primary
Disconnects
-
Figure
12
is
a
side
view
of
the
circuit
breaker
with
a
side
phase
barrier
removed
to
show
details
of
the
primary
disconnects
.
Each
circuit
breaker
has
three
upper
and
three
lower
primary
disconnects
.
Upper
primary
discon
-
nects
are
connected
to
the
stationary
contacts
of
the
vacuum
interrupters
,
and
the
lower
primary
disconnects
to
the
movable
contacts
.
Each
disconnect
arm
has
a
set
of
multiple
spring
loaded
fingers
that
mate
with
bus
bars
in
the
metal
-
clad
switchgear
.
The
number
of
fingers
in
the
disconnect
assembly
varies
with
the
continuous
and
/
or
momentary
rating
of
the
circuit
breaker
.
There
are
three
insulating
push
rods
.
Each
push
rod
connects
the
movable
contact
of
one
of
the
vacuum
interrupters
to
the
jack
shaft
driven
by
the
closing
and
tripping
mechanism
.
Flexible
connectors
ensure
secure
electrical
connections
be
-
tween
the
movable
contacts
of
each
interrupter
and
its
bottom
primary
disconnect
.
Phase
Barriers
-
Phase
barrier
configurations
vary
among
GMI
breakers
depending
on
voltage
and
continuous
current
ratings
.
Figure
13
is
a
rear
view
of
a
circuit
breaker
that
shows
the
two
outer
(
phase
to
ground
)
insulating
barriers
and
two
interphase
barriers
.
The
interphase
barriers
are
not
provided
on
all
circuit
breaker
ratings
.
These
four
plates
of
glass
polyester
insulating
material
are
attached
to
the
circuit
breaker
and
provide
suit
-
able
electrical
insulation
between
the
vacuum
interrupter
pri
-
mary
circuits
and
the
housing
.
Stored
Energy
Operating
Mechanism
The
stored
energy
operating
mechanism
of
the
GMI
circuit
breaker
is
an
integrated
arrangement
of
springs
,
solenoids
and
mechanical
devices
designed
to
provide
a
number
of
critical
functions
.
The
energy
necessary
to
close
and
open
the
contacts
of
the
vacuum
interrupters
is
stored
in
powerful
tripping
and
closing
springs
.
These
springs
are
normally
charged
automatically
,
but
there
are
provisions
for
manual
charging
.
The
operating
mechanism
that
controls
charging
,
closing
and
tripping
functions
is
fully
trip
-
free
,
i
.
e
.
,
spring
charging
does
not
automatically
change
the
position
of
the
primary
contacts
,
and
the
closing
function
may
be
overridden
by
the
tripping
function
at
any
time
.
Note
:
Two
different
latch
systems
have
been
used
in
GMI
circuit
breakers
,
with
changeover
from
one
design
to
the
other
occurring
in
mid
-
1991
.
This
instruction
manual
describes
both
designs
.
Pages
10
-
11
describe
the
operation
of
the
mechanism
used
beginning
in
approximately
mid
-
1991
.
Pages
12
-
13
describe
the
operation
of
the
mechanism
used
from
1989
until
approximately
mid
-
1991
.
f
BJ
**
;
j
|
;
;
v
>
.
.
.
.
tfvirnnv
Figure
12
:
Upper
and
Lower
Primary
Disconnects
.
Figure
13
:
Breaker
with
Interphase
and
Outerphase
Barriers
.
9
Courtesy of NationalSwitchgear.com