Electrical connection of the flame detector 
It is important to achieve practically disturbance- and loss-free signal transmission: 
  Never run the detector cable together with other cables 
– Line capacitance reduces the magnitude of the flame signal 
– Use a separate cable 
  Observe the permissible cable lengths (refer to «Technical data») 
Commissioning notes 
When commissioning the plant or when doing maintenance work, make the following 
safety checks: 
 
  Safety check to be carried out  Anticipated response 
a)  Burner startup with flame detector darkened  Lockout at the end of safety time (TSA) 
b)  Burner startup with flame detector exposed to 
extraneous light 
Lockout after 40 seconds at the latest 
c)  With wire strap «B»: 
Simulation of loss of flame during operation. For that 
purpose, darken the flame detector during operation 
and maintain that state 
Lockout 
d)  Without wire strap «B»: 
Simulation of loss of flame during operation. For that 
purpose, darken the flame detector during operation 
and maintain that state 
Repetition followed by lockout at the end of «TSA» 
e) 
Burner startup with response of air pressure switch  Prevention of startup/lockout during prepurge time 
f) 
Burner operation with simulated air pressure failure  Immediate lockout 
Engineering notes 
  Install switches, fuses, earthing, etc., in compliance with local regulations 
  Connect valves and other plant components as specified in the burner 
manufacturer’s documentation 