Technical data (cont'd) 
Voltage at the ionization probe 
- Operation 
- Test 
 
C 330 V ±10 % 
C 380 V ±10 % 
Short-circuit current  max. 0.5 mA 
Recommended range of measuring  
instrument 
0...50 µA 
Perm. length of detector cable 
- Normal cable, laid separately ²) 
- Shielded cable 
 
max. 80 m 
max. 140 m (e.g. high-frequency cable; 
shielding connected to terminal 22) 
Required detector current in operation  min. 6 µA 
Possible detector current in operation  max. 200 µA 
 
Supply voltage 
- Operation 
- Test 
 
C 330 V ±10 % 
C 380 V ±10 % 
Required detector current  min. 70 µA 
Possible detector current 
- Operation 
- Test 
 
max. 700 µA 
max. 1000 µA ¹) 
Perm. length of detector cable 
- Normal cable, laid separately ²) 
- Shielded cable 
 
max. 100 m 
max. 200 m (e.g. high-frequency cable; 
shielding connected to terminal 22) 
 
¹) 
During the prepurge time with higher test voltage: Self-ignition and extraneous light test 
²) 
Multicore cable not permitted 
Detector current measurement 
Ionization probe  Flame detector QRA2 / QRA4 / QRA10 
 
LFL1...
24
7451v01/0204
M
C
+
+
-
ION
 
7451v02/0204
A
M
C
23
22
LFL1...
-
+
-
+
QRA...
 
For detector currents, refer to «Technical data». 
 
C  Electrolytic condenser 100...470 µF; DC 10...25 V
ION Ionization probe 
M  Microammeter Ri max. 5,000 
Flame supervision with 
ionization probe 
Flame supervision with 
flame detector QRA2 / 
QRA4 / QRA10 
Measuring circuit for 
detector current 
measurement 
Legend