16/25 
Building Technologies Division    CC1N7451en 
  20.11.2017 
Startup sequence (cont'd) 
Interrupted pilot burners 
 
t3 
t3´ 
Preignition time 
Release of fuel for pilot burner via terminal 17 
 
 
TSA 
TSA´ 
Ignition safety time 
On completion of «TSA», a flame signal must be present at terminal 22. It must not be interrupted until 
controlled shutdown takes place 
 otherwise non-volatile lockout 
 
 
t4 
t4´ 
Interval «ZBV-BV1» 
Up to the release of the fuel valve at terminal 19 for the main burner’s start load 
 
 
t9 Second safety time 
On completion of the second safety time, the main burner must have been ignited by the pilot burner since 
terminal 17 becomes dead as soon as this time has elapsed, causing the pilot valve to close 
 
 
B  Operating position of the burner 
 
 
B-C Burner operation 
-
  During burner operation, «LR» drives the air damper to the high-fire or low-fire position, depending on 
the demand for heat 
-  Release of high-fire is enabled by auxiliary switch «v» in the actuator 
-  In the event of loss of flame during operation, the LFL1… will initiate lockout 
 
 
C Controlled shutdown 
On controlled shutdown, the «BV...» will immediately be closed. At the same time, the sequence switch 
starts and programs «t6» 
 
 
C-D  The sequence switch travels to start position «A», postpurging 
When burner off time starts, control terminals 11 and 12 carry voltage to drive the air damper to the fully 
CLOSED position. Flame signal supervision also remains active during burner off times 
   
t6 Postpurge time 
-
  Fan «M2» connected to terminal 7 
-  Shortly after the start of «t6», power is fed to terminal 10 
 air damper will be driven to the MIN position 
-  Full closing of the air damper starts only shortly before «t6» has elapsed 
 triggered by the control signal at terminal 11 
-  During the following burner off period, terminal 11 remains live 
 
 
t13  Permissible afterburn time 
During «t13», the flame signal input can still receive a flame signal 
 no lockout 
   
D-A  End of control sequence 
 start position 
As soon as the sequence switch has reached the start position – thereby switching itself off – the flame 
detector and extraneous light test will start again. 
During burner off periods, the flame supervision circuit is live. A faulty flame signal of a few seconds will 
initiate lockout. 
Short ignition pulses of the UV tube, caused for instance by cosmic radiation, do not lead to lockout. 
 
Times «TSA´», «t3´» and «t4´» only exist with burner controls of the 01 series.