Connection examples and program sequence
Doubling the safety time with direct
spark flame burners
16
Z
N
17
18
BV1
19
BV2
7451a10/1295
Only with burner controls of the 01
series.
This circuit change (linking terminals
17 and 18) reduces the preignition
time by 50 %.
Extension of the safety time is only permitted if in compliance with the
relevant national standards.
Burner without air damper
11
10
86
7451a11/0396
M
N
If the case of burners with no air
damper (or with an air damper not
controlled and monitored by the
burner control), terminals 8 and 6
must be linked, as otherwise the
burner control will not be able to start
the burner.
Reversed polarity protection with
AGM30
A
GM30
1 23
Black
Brown
If the mains cables (L-N) are
switched, the AGM30 simulates a
flame signal (extraneous light). The
burner initiates lockout.
2-stage direct spark flame burner
16
Z
N
17
18
BV1
BV2
SA
LR
19
9
20
11
10
8
LK
11
7
1
6
5
2
10
8
9
4
3
N
12
13
IV
I
M
II
III
7451a03/0396
L...
LR
SA
BV1/BV2
Load control by a 2-position controller. The air damper is
closed during burner off periods.
min.
0...
100%
R
M1
M2
Z
BV1
LR
BV2
FS
A
B
C
D
7451a06/0600
T
P
M
R
M
LK
~
t7 t1
t6
t3
TSA
t4
t5
t11
t12
t13
Control of actuator «SA» according to the single-wire
principle (actuator «SA»: E.g. SQN3... according to Data
Sheet N7808). For other connections, refer to
«Connection diagrams».