System reactions on SINAMICS alarms
08/2005 System Reactions on Alarms
5-991
© Siemens AG, 2005. All rights reserved
SINUMERIK 840D sl/840D/840Di/810D Diagnostics Guide (DA), 08/2005 Edition
5.2 System reactions on SINAMICS alarms
The errors and states detected by the individual components of the drive system
are indicated by alarms.
These alarms are categorized into faults and warnings.
General information on faults (alarms)
The following happens when a fault occurs:
• The appropriate fault action is triggered.
• Status signal ZSW1.3 is set.
• The fault is entered in the fault buffer.
Clearing of a fault:
• Clear the cause of the fault
• Acknowledge the fault
General information on warnings (alarms)
The following happens when a warning occurs:
• Status signal ZSW1.7 is set.
• The warning is entered in the warning buffer.
Clearing of a warning:
• Warnings are self-acknowledging, i.e. if the cause has been removed, the
warnings reset themselves automatically.
"Reaction" to faults (alarms)
The standard fault reaction specifies the reaction in the event of a fault.
For an overview of parameters and function block diagram, please refer to the fol-
lowing publication:
LIS1, Lists 1
Definition of fault reactions
Description NONE
Reaction None
Description No reaction when a fault occurs

Other manuals for Siemens MCP 398C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens MCP 398C and is the answer not in the manual?

Siemens MCP 398C Specifications

General IconGeneral
BrandSiemens
ModelMCP 398C
CategoryControl Systems
LanguageEnglish

Related product manuals