Parameter Function Range
[Default]
Description / Notes
P111 Inverter power rating (kW/hp) 0 - 50.00
[]
Read-only parameter that indicates the power rating of the inverter in kW. e.g. 0.55 = 550 W
Note: If P101 = 1 then the rating is displayed in hp.
P121 Enable/disable RUN button 0 - 1
[1]
0 = RUN button disabled
1 = RUN button enabled (only possible if P007 = 1)
P122 Enable/disable FORWARD/REVERSE
button
0 - 1
[1]
0 = FORWARD/REVERSE button disabled
1 = FORWARD/REVERSE button enabled (only possible if P007 = 1)
P123 Enable/disable JOG button 0 - 1
[1]
0 = JOG button disabled
1 = JOG button enabled (only possible if P007 = 1)
P124
Enable/disable n and o buttons
0 - 1
[1]
0= n and o buttons disabled
1= n and o buttons enabled (only possible if P007 = 1)
Note: This applies for frequency adjustment only.
P131 Frequency setpoint (Hz) 0 - 200.00
[-]
P132 Motor current (A) 0 - 99.9
[-]
P134 DC link voltage (V) 0 - 1000
[-]
Read-only parameters. These are copies of the values stored in P001 but can be accessed
directly via the serial link.
P135 Motor RPM 0 - 9999
[-]
P137 Motor voltage (V) 0 - 1000
[-]
P910 • Local/Remote mode 0 - 4
[0]
Sets the inverter for local control or remote control over the serial link:
0 = Local control
1 = Remote control (and setting of parameter values)
2 = Local control (but remote control of frequency)
3 = Remote control (but local control of frequency)
4 = Local control (but remote read and write access to parameters and facility to reset trips)
Note: When operating the inverter via remote control (P910 = 1 or 3), the analogue input remains
active when P006 = 1 and is added to the setpoint.
P922 Software version 0 - 9999
[-]
Contains the software version number and cannot be changed.
P923 • Equipment system number 0 - 255
[0]
You can use this parameter to allocate a unique reference number to the inverter. It has no operational
effect.
P930 Most recent fault code 0 - 9999
[-]
The last recorded fault code is stored in this parameter. It is cleared when the inverter is reset.
Note: The warning may be cleared by attempting to change its value.
P931 Most recent warning type 0 - 9999
[-]
The last recorded warning is stored in this parameter until power is removed from the inverter:
002 = Current limit active
003 = Voltage limit active
004 = Slip limit exceeded
005 = Motor overtemperature
Note: The warning may be cleared by attempting to change its value.
P944 Reset to factory default settings 0 - 1
[0]
Set to `1' and then press P to reset all parameters except P101 to the factory default settings.
P971 •
EEPROM storage control 0 - 1
[1]
0 = Changes to parameter settings are lost when power is removed.
1 = Changes to parameter settings are retained during periods when power is removed.