EasyManua.ls Logo

Siemens OOH941 User Manual

Siemens OOH941
8 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
A6V10324659_en--_j
SIEMENS Industry, Inc.
2020-08-28
Smart Infrastructure
Installation Instructions
Model OOH941
Multi-Criteria Fire Detector
UL268 7th edition listed
Figure 1
These instructions are written in accordance with the
installation guidelines of NFPA 72, National Fire Alarm
Code and CAN/ULC-S524, The Installation of Fire
Alarm Systems. The model OOH941
detector (as shown
in Figure 1) meets the VEWFD (Very Early Warning Fire
Detector) classification and sensitivity requirements of
NFPA 76 (Standard for the Fire Protection of
Telecommun
ications Facilities) incorporating a
programmable “Alert” (Pre-
Alarm) sensitivity threshold of
0.2%/ft obscuration and an “Alarm” sensitivity threshold
of 1.0%/ft obscuration.
CAUTION
DO NOT install this detection device until all construction
is completed.
DO NOT store this detection device where it can be
contaminated by dirt, dust, or humidity.
DETECTOR PLACEMENT
Although no specific spacings are set for the detectors
used for a clean air application, for multi-
criteria fire
detection use 30-foot
center spacing (900 sq ft) from
NFPA 72 initiating devices chapter, if practical, as a
guide or starting point for a detector installation layout.
This spacing, however, is based on ideal conditions
smooth ceiling, no air movement, and no physical
obstru
ctions. In some applications, therefore,
considerably less area is protected adequately by each
smoke detector. This is why it is mandatory to closely
follow the installation drawings. In all installations place
the detector on the ceiling, a minimum of 6
a side wall, or on a wall, 12 inches from the ceiling.
For thermal detection, use the matrix below:
Spacing, Feet Temperature Rating, °F With/without Guard Model
50
135, 145, 155, 165, 175
With and without STI Guard
60 135, 145, 155, 165, 175
70 135, 145
Drawings provided or approved by Siemens Industry,
Inc., or by its authorized distributors are extremely
important.
The detector placements shown on these
drawings were chosen after a careful evaluation of the
area that is protected. Such factors as air currents,
temperature, humidity, pressure, and the nature of the
fire load were carefully considered. Especially note
d
were the room or area configuration and the type of
ceiling (sloped or flat, smooth or beamed). Siemens
Industry, Inc.’s extensive experience in the design of the
system assures the best detector placement by following
these drawings. Sound engineering j
udgment by
qualified personnel must be followed.
TO AVOID NUISANCE ALARMS
Do not locate the detectors where excessive smoke
concentrations exist under normal conditions, or in areas
of prolonged high relative humidity where condensation
occurs.
Do not locate the detectors next to an oil burner,
or
garage where exhaust fumes can trigger an alarm. Other
causes of false alarm are dust accumulation, heavy
concentrations of steam, heavy pipe or cigar smoke, and
certain aerosol sprays.
Question and Answer IconNeed help?

Do you have a question about the Siemens OOH941 and is the answer not in the manual?

Siemens OOH941 Specifications

General IconGeneral
BrandSiemens
ModelOOH941
CategorySecurity Sensors
LanguageEnglish

Summary

Installation Instructions

Detector Placement

Guides on optimal location and spacing for fire detectors in various conditions.

Nuisance Alarm Avoidance

Recommendations to prevent false alarms from environmental factors like steam or dust.

Detector Environment and Operation

Environmental Considerations

Details on air currents, ceiling factors, temperature, humidity, and air velocity.

LED Indicator Operation

Explains the meaning of different LED color and flash patterns for detector status.

Detector Programming

Instructions for setting detector addresses and selecting application profiles.

Electrical and Wiring

Electrical Specifications

Details on supply voltage and current consumption for the detector.

Wiring Configurations

Guidance on polarity insensitive and isolator mode wiring methods.

Installation and Testing Procedures

Detector Mounting

Recommended orientation and steps for mounting the detector head into its base.

Detector Testing

Procedures for functional and sensitivity testing of detectors.

Sensitivity Measurement

How to measure detector sensitivity using the DPU device.

Maintenance and Replacement

Recommended Wall Mounting

Detailed guidance on wall mounting orientation and detector guard.

Smoke Detector Functional Test

How to perform a functional smoke entry test using test gas.

Detector Replacement

Instructions for replacing older detectors with newer versions.

Detector Maintenance

Information on trouble messages indicating detector replacement needs.

Special Applications and Compliance

Special Application Profiles

Details on selectable application profiles, especially for Telecommunications.

Method to Configure Sensitivity

How to select special application sensitivity via control panel.

FCC Statement

Compliance information regarding radio frequency energy and interference.

Related product manuals