EasyManua.ls Logo

Siemens OpenAir GCA Series - Specifications

Siemens OpenAir GCA Series
23 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
OpenAirGCA Series Spring Return 160 lb-in Electronic Damper Actuator Technical Instructions
Document No. 155-173P25
May 19, 2014
Siemens Industry, Inc. Page 3
Specifications
Ambient
Conditions
Ambient temperature
operation -25°F to 130°F (-32°C to 55°C)
storage and transport -40°F to 158°F (-40°C to 70°C)
Ambient humidity (non-condensing) 95% rh
Agency
Certification
Conformity
UL listed to UL60730
(to replace UL873)
cUL certified to Canadian Standard
C22.2 No. 24-93
Electromagnetic compatibility (EMC) 2004/108/EC
Immunity for all models, except GCA132.xx EN61000-6-2
Immunity for GCA132.xx EN61000-6-1
Emissions for all models EN61000-6-3
Power
Supply
GCA16x GCA15x GCA13x GCA12x GCA22x
24 Vac ± 20%
24 Vdc ± 10%
24 Vac ± 20%
24 Vdc ± 10%
24 Vac± 20%
24 Vdc ± 10%
24 Vac ±
20%
24 Vdc ±
10%
120 Vac ±
10%
Frequency
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
Power Consumption
running
7 VA/5W 7 VA/5W 7 VA/5W 7 VA/5W 8 VA
holding
5 VA/3W
5 VA/3W
5 VA/3W
5 VA/3W
6 VA
Control Signal
GCA16x
GCA15x
GCA13x
GCA12x
GCA22x
Input Signal
(YG0)
voltage input
0 to 10 Vdc
(max. 35 Vdc)
0 to 10 Vdc or
2 to 10 Vdc
(max. 35 Vdc)
Floating
2-Position
2-Position
input resistance
>100K ohms
>100K ohms
Feedback
Signal
GCA16x
GCA15x
GCA13x
GCA12X
GCA22x
Position output signal
(U-G0)
voltage output
0 to 10 Vdc
0 to 10 Vdc
0 to 1000 ohms
<10 Ma
(GCA 132x only)
Load <1W
maximum output
current
±1 mA
+1 mA,
-.5 mA
Function
Running/spring return torque
Operating with 24 Vac 160 lb-in (18 Nm)
Maximum torque <360 lb-in (40 Nm)
Runtime for 90°
operating with motor 90 sec
closing (on power loss) with spring return 15 seconds typical
NOTE: At -25°F, spring return is 142 lb-in (16 Nm
).
Equipment rating
Class 2, in accordance with UL/CSA