OpenAir™ GCA Series Spring Return 160 lb-in Electronic Damper Actuator Technical Instructions
Document No. 155-173P25
May 19, 2014
Siemens Industry, Inc. Page 3
Specifications
Conditions
operation -25°F to 130°F (-32°C to 55°C)
storage and transport -40°F to 158°F (-40°C to 70°C)
Ambient humidity (non-condensing) 95% rh
Certification
Conformity
(to replace UL873)
cUL certified to Canadian Standard
C22.2 No. 24-93
Electromagnetic compatibility (EMC) 2004/108/EC
Immunity for all models, except GCA132.xx EN61000-6-2
Immunity for GCA132.xx EN61000-6-1
Emissions for all models EN61000-6-3
Supply
GCA16x GCA15x GCA13x GCA12x GCA22x
24 Vdc ± 10%
24 Vdc ± 10%
24 Vdc ± 10%
20%
24 Vdc ±
10%
10%
—
running
7 VA/5W 7 VA/5W 7 VA/5W 7 VA/5W 8 VA
(Y–G0)
voltage input
(max. 35 Vdc)
2 to 10 Vdc
(max. 35 Vdc)
Signal
(U-G0)
voltage output
<10 Ma
(GCA 132x only)
Load <1W
current
-.5 mA
Running/spring return torque
Operating with 24 Vac 160 lb-in (18 Nm)
Maximum torque <360 lb-in (40 Nm)
Runtime for 90°
operating with motor 90 sec
closing (on power loss) with spring return 15 seconds typical
NOTE: At -25°F, spring return is 142 lb-in (16 Nm
).
Class 2, in accordance with UL/CSA