EasyManua.ls Logo

Siemens PAD-3

Siemens PAD-3
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
16
2.5.7 AC Fail Relay
AC Fail Relay provides a normally open (N.O.) Form “A” contact which will be de-energized without delay
if AC is low or lost. It provides a local signal (audible and visual) of AC fail at the protected premises but
will not cause the DACT to signal.
3+
1+
3-
1-
4+
2+
4-
2-
TB13
TB12
1
2
3
4
5
6
9
10
11
12
13
14
Input 1
EOL 24K
½W 5%
P/N 140-820405
Input 2
Trouble
Relay
NAC
7
8
AC Fail
1+
1-
2+
2-
TB3
FS-250
LOOP CKT
*
EOL
3.6K, 1/4W
P/N 140-830185,
or
470 OHMS, 1/4W
P/N 140-820164,
as applicable
*
EOL
1
2
3
4
5
HTRI-S
#1
1
2
3
4
5
HTRI-S
#2
PAD-3
*
EOL
FS-DLC LOOP
NOTES:
1. Program HTRI-S #1 as Status causing, which will not cause the DACT
to signal but will cause local visual and audible signal. It provides a local
signaling of AC fail at the protected premises.
2. Program HTRI-S #2 as Trouble causing, which will cause the DACT to
signal for all common troubles (including AC fail with reporting delay).
Figure 2-12. AC Fail Relay Connection Example
2.6 Ground Fault Detection Enable/Disable
For some applications (when used with RSA-Series annunciators, for instance), the PAD-3 is used to
provide power to an auxiliary device which gets a control signal from a fire alarm panel. The ground fault
reference for the PAD-3 may be different than the reference used by the fire alarm panel, resulting in a
ground fault trouble at the panel even when none exists. To remedy this condition, the PAD-3 can have
its ground fault detection circuit disabled. Once disabled, the fire alarm panel’s ground fault detection
circuitry will detect any ground fault in the system. See Section 5-2 for correct positioning of this jumper,
and see Figure 2-2 for the location of this jumper.

Related product manuals