Page 1 of 16
Product Description
The Economizer Controller allows the use of
unconditioned outside air to cool a building. The
Free Cooling air determination is based on customer
temperature and humidity selections, as well as
optional Demand Control Ventilation (DCV)
strategies with CO
2
level selection.
Features
• Economizer control provides “free cooling”
based on single or dual dry bulb temperature, or
combination temperature + humidity sensors.
• Wide temperature shut-off setpoint range
selection and Btu/lb selection range selectable
by DIP switches.
• Potentiometers allow accurate adjustment of
DCV, exhaust fan levels, and minimum damper
position.
• Versions with remote minimum position damper
adjustments accept either 0 to 10 Vdc or 135
Ohm potentiometer signals.
• Used with Siemens OpenAir
®
damper actuators.
• Flexible sensor inputs accept 10K or 3K
standard NTC sensors, or Siemens QFM2160U
combination temperature/humidity 0 to 10V
sensor for enthalpy control.
• LED Indication when in Free Cooling operation,
DCV operation and exhaust fan operation as
well as during sensor failure.
• Quick installation and easy commissioning.
• Two-stage cooling control.
• Occupancy input with default capability.
• Quick connect I/O with 1/4” spade connections.
• Anti-freeze protection.
• Brownout protection.
Product Numbers
Prerequisites
For proper Economizer Controller operation, read
this User Guide carefully, and follow the instructions
in the Economizer Controller Start-up/
Commissioning Mode section. Failure to do so may
result in damage to the product or create a
hazardous condition. Installation of this controller
must be performed by a trained HVAC service
technician.