25
Testing First Generation Trip Devices
Bench Testing
The alligator clips described previously are also used to make
connections to the first generation trip devices for bench
testing, so connections and procedures are the same as
when testing with the device on the circuit breaker.
1. Types
A — Dual Static (long time an instantaneous
elements).
C —Dual Static Selectable Time Band and
high range instantaneous.
D —Selective Static (long time and short time
elements)
AG —Dual Static with ground fault element for 3
wire circuits.
DG —Selective Static with ground fault element
for 3 wire circuits.
4WAG —Dual Static with ground fault element for 4
wire and 3 wire circuits.
4WDG —Selective Static with ground fault element
for 4 wire and 3 wire circuits.
2. The pick-up settings of the instantaneous and short time
delay elements are calibrated at 3, 5, 8 and 12 multiples
of the long time delay pick-up setting.
3. The maximum interrupting time is the maximum length
of time that fault current flows, including arcing time.
4. Instantaneous maximum interrupting time may be greater
when breakers are closed in on a fault depending on
actual fault conditions. The maximum potential increase
for a 3 phase fault is 0.01 seconds and for a single phase
ground fault is 0 02 seconds.
5 The lower limit of ground fault recognition is 25 amperes
for an LA-600 breaker. For an LA-1600 breaker the
lower limit is 40 amperes. Application of Models 4WAG
and 4WDG is not recommended for LA-600 breakers
having a minimum continuous current setting of less than
75 amperes or an LA-1600 breaker with a minimum
continuous current setting of less than 200 amperes.
Dual Device
MODEL A—general purpose device normally used for phase
overcurrent protection. The pick-up range is selected from
the trip rating table and is continuously adjustable from “A”
through “E” in the field. The instantaneous element is continu-
ously field adjustable from 3 to 12 multiples of the long time
delay pickup settings selected. The time delay band is
selected and set at the factory—it is not field adjustable.
Available time delays are minimum, intermediate and maxi-
mum
MODEL AG (optional)—provides phase overcurrent protec-
tion plus sensitive ground fault overcurrent protection for
systems with phase-to-phase loading. Ground current pick-
up settings are independent of the phase pick-up settings,
and continuously adjustable in the field from 20% through
80% of the minimum phase pick-up setting shown in column
“A “
MODEL 4WAG (optional)—provides phase overcurrent pro-
tection plus sensitive ground fault overcurrent protection for
3 wire and 4 wire circuits for systems with phase-to-neutral
loading. Ground current pick-up settings are independent of
the phase pick-up settings, and continuously adjustable in
the field from 20% through 80% of the minimum phase pick-
up setting in column “A.”
MODEL C (optional)—Dual Static Selectable Time Band and
high range instantaneous.
MODEL D (optional)—an overcurrent trip device which pro-
vides time delay tripping only. It allows field adjustment of
long time delay and pick-up and short time delay and pick-
up. The continuous adjustment feature allows a setting
selection anywhere within calibrated points. The user can
adjust the current at which the device transfers from long time
to short time delay between these limits. Any one of the three
short time delay curves can be chosen to be used with any
of the three long time delay curves.
MODEL DG (optional)—provides phase overcurrent protec-
tion plug sensitive ground fault overcurrent protection for
systems with phase-to-phase loading. Ground current pick-
up settings are independent of the phase pick-up settings,
and continuously adjustable in the field from 20% through
80% of the minimum phase pick-up setting shown in column
“A.”
MODEL 4WDG (optional)—provides phase overcurrent pro-
tection plus sensitive ground fault overcurrent protection for
3 wire and 4 wire circuits for systems with phase-to-neutral
loading. Ground current pick-up settings are independent of
the phase pick-up settings, and continuously adjustable in
the field from 20% through 80% of the minimum phase pick-
up setting in column “A.”