CB1B1420en_01/ 2013-03-07 Subject to alteration Siemens Building Technologies
Are your rooms too warm/too cold?
+
Press + or to increase or decrease the room
temperature setpoint in increments of 0.5 °C /
1 °F. Proceed as follows:
Press + or to adjust the setpoint
temporarily.
Press to save the value or wait for the
program to exit automatically.
To permanently modify the temperature
setpoints, use parameters P05 and P07.
To lock the setpoints, use parameters P06
and P08.
Does symbol appear on the display?
(Only with battery-powered version)
Symbol is displayed when the batteries are low.
Replace them with 2 new alkaline batteries type AAA.
Proceed as follows:
Get 2 new alkaline batteries type AAA
Remove the battery holder, then the batteries, insert
the new batteries and, within 1.5 minutes, replace the
battery holder
Ensure the exhausted batteries are disposed of
correctly, in compliance with environmental
requirements
Do you want to change parameters?
+
If you want to change control parameters,
proceed as follows:
Press + and simultaneously for 5 seconds
Release them and parameter "P02" is
displayed
Press + or to scroll to the parameter that
needs to be adjusted
Press to select this parameter
Press + or to adjust the value
Press to confirm and save the adjusted
value
Select and modify other parameters
The program automatically returns to the
normal screen after a timeout.
Parameter list
Parameter
no.
Description Setting range (default)
P02 Selection of °C
or °F
1 = °C (default)
2 = °F
P03 Standard
temperature
display
1 = room temperature
(default)
2 = setpoint
P04 Temperature
sensor
calibration
-3…3 °C
Step 0.5 °C
(-6…6 °F, step 1 °F)
Default: 0 °C
P05 Comfort setpoint 5…35 °C, step 0.5 °C
(41…95 °F, step 1 °F)
Default: 20 °C, 68 °F
P06 Comfort setpoint
lock
0 = OFF (default)
1 = ON locked according
to setting in P05
P07 Economy
setpoint
5…35 °C, step 0.5 °C
(41…95 °F, step 1 °F)
Default: 16 °C, 61 °F
P08 Economy
setpoint lock
0 = OFF (default)
1 = ON locked according
to setting in P07
P09 Buzzer 0 = OFF
1 = ON (default)
P10 Show frost
protection icon
0 = OFF (default)
1 = ON
P21 Button scanning
rate for the
capacitive
buttons (touch
keys, RDD100.1
only)
Note: a shorter
scanning rate
means shorter
battery life.
0.2 = 0.25 s
0.5 = 0.5 s
1.0 = 1.0 s (default)
1.5 = 1.5 s
P22 Reload factory
settings
0 = OFF (default)
1 = Reload
P23 Software version
information
No adjustment possible