EasyManuals Logo

Siemens RDF301.50 Series Instructions

Siemens RDF301.50 Series
17 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #3 background imageLoading...
Page #3 background image
Temporary Comfort mode extension.
1- or 3-speed fan control (automatically or manually).
Display of current room temperature or setpoint in °C and/or °F.
Minimum and maximum limitation of room temperature setpoint.
Button lock (automatically and manually).
2 multifunctional inputs, freely selectable for:
Sensor for automatic heating / cooling changeover
External room temperature or return air temperature sensor
Dew point sensor
Electric heater enable
Fault input
Monitor input for temperature sensor or switch state
RDF301…:
Operating mode switchover contact … (keycard, window contact, etc )
RDF600KN:
Window contact
Presence detector
Advanced fan control function, e.g. fan kick, fan start, selectable fan operation
(enable, disable or depending on heating or cooling mode).
Purge function together with 2-port valve in a 2-pipe changeover system.
Reminder to clean fan filters (adjust with P62).
Floor heating temperature limitation.
Reload factory settings for commissioning and control parameters.
KNX bus (terminals CE+ and CE-) for communication with Synco or KNX
compatible devices.
Display of outdoor temperature or time of day via KNX bus.
Time scheduling and central control of setpoints via KNX bus.
With a Synco RMx7xx controller, the energy demand signal of the thermostat is
used to optimize energy supply.
RDF301.50 only:
Four buttons to control KNX actuators via KNX S-mode.
("switching groups" with functions such as switching, dimming, blinds control,
8-bit scene).
RDF301.50H only:
Four buttons for Hotel applications to control via KNX S-mode.
Same functions as RDF301.50, but with dedicated button labels for hotel
applications: Make Up Room (MUR), Do Not Disturb (DND).
Applications
The thermostats support the following applications, which can be configured using
the DIP-switches on the inner side of the thermostat's front panel or a commissio-
ning tool.
All DIP switches need to be set to OFF (remote configuration, factory setting) to
select an application via commissioning tool.
Remote configuration
, via commissioning tool (factory set)
Synco ACS
ETS
DIP switches
1
ON
2 3
Remote configuration
3 / 17
Siemens RDF301, RDF301.50..., RDF600KN CE1N3171en
Building Technologies Semi flush-mount communicating room thermostats 2014-05-23

Other manuals for Siemens RDF301.50 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens RDF301.50 Series and is the answer not in the manual?

Siemens RDF301.50 Series Specifications

General IconGeneral
BrandSiemens
ModelRDF301.50 Series
CategoryThermostat
LanguageEnglish

Related product manuals