EasyManuals Logo

Siemens RDF301.50 Series User Manual

Siemens RDF301.50 Series
20 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #3 background imageLoading...
Page #3 background image
3 / 20
Siemens RDF301, RDF301.50..., RDF600KN, RDF600KN/VB, RDF600KN/S CE1N3171en
Smart Infrastructure Semi flush-mount communicating room thermostats 2020-02-21
Functions
· Room temperature control via built-in temperature sensor or external room
temperature / return air temperature sensor.
· Changeover between heating and cooling mode (automatically via local sensor
or bus, or manually).
· Selection of applications via DIP switches or commissioning tool.
· Selection of operating mode via operating mode button on the thermostat.
· Temporary Comfort mode extension.
· 1-speed or 3-speed fan control (automatically or manually).
· Display of current room temperature or setpoint in °C and/or °F.
· Minimum and maximum limitation of room temperature setpoint.
· Button lock (automatically and manually).
· 2 multifunctional inputs, freely selectable for:
- Sensor for automatic heating/cooling changeover
- External room temperature or return air temperature sensor
- Dew point sensor
- Electric heater enable
- Fault input
- Monitor input for temperature sensor or switch state
RDF301…:
- Operating mode switchover contact … (keycard, window contact, etc )
RDF600KN…
- Window contact
- Presence detector (standard presence and hotel presence)
· Advanced fan control function, e.g. fan kick, fan start, selectable fan operation
(enable, disable* or depending on heating or cooling mode).
· Purge function together with 2-port valve in a 2-pipe changeover system.
· Reminder to clean fan filters (adjust with P62).
· Floor heating temperature limitation.
· Reload factory settings for commissioning and control parameters.
· KNX bus (terminals CE+ and CE-) for communication with Synco or KNX
compatible devices.
· Display of outdoor temperature or time of day via KNX bus.
· Time scheduling and central control of setpoints via KNX bus.
· With a Synco RMx7xx controller, the energy demand signal of the thermostat is
used to optimize energy supply.
* On RDF301 and RDF301.50, it is recommended that the fan is running in
deadzone, i.e. P60=0, or using a return air- or external temperature sensor.
RDF301.50, RDF600KN/S only:
· Four buttons to control KNX actuators via KNX S-mode.
("Switching groups" with functions such as switching, dimming, blinds control,
8-bit scene).
RDF301.50H only:
· Four buttons for Hotel applications to control via KNX S-mode.
Same functions as RDF301.50, but with dedicated button labels for hotel
applications: Make Up Room (MUR), Do Not Disturb (DND).

Other manuals for Siemens RDF301.50 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens RDF301.50 Series and is the answer not in the manual?

Siemens RDF301.50 Series Specifications

General IconGeneral
BrandSiemens
ModelRDF301.50 Series
CategoryThermostat
LanguageEnglish

Related product manuals