Siemens RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation CE1P3181en
Building Technologies Functions 14 Dec 2011
Modulating control: 3-position or PWM
The diagrams below show the control sequence of modulating PI control.
Heating mode with manual selection (P01=2) Cooling mode with manual selection P01=2)
Y [%]
100
0
w
3181D1124b
T[°C]
XpH
YH
YE
w
D
½ SDH ½ SDH
3181D105b
Y [%]
100
0
w
T[°C]
YC
XpC
Heating and cooling mode (P01=4)
T[°C] Room temperature
w Room temperature setpoint
YE Control. command “El. heater"
(only on/off)
YH Control command “Valve” or “Comp.” (H)
(only PWM, not 3-position)
YC Control command “Valve” or “Comp.” (C)
XpH Proportional band “Heating” (P30)
XpC Proportional band “Cooling” (P31)
X
dz
Dead zone (P33)
Y [%]
100
0
w
3181D114b
T[°C]
YC
XpH
YH
XpC
½
x
dz
½
x
dz
YE
w
D
½ SDH ½ SDH
w
D
Setpoint differential (P34)
The diagrams only show the PI controller’s proportional part.
Setting the sequence and the control outputs
Refer to sections 4.5 ("Applications"), 4.7.1 ("Sequences") and 4.7.2 ("Outputs").
Y1 can only be on/off or PWM
Y2 can only be on/off
Y3 can be on/off, PWM or 3-position
Note
Notes

Other manuals for Siemens RDG110

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens RDG110 and is the answer not in the manual?

Siemens RDG110 Specifications

General IconGeneral
BrandSiemens
ModelRDG110
CategoryThermostat
LanguageEnglish

Related product manuals