INTRODUCTION The Model RPM from Siemens Industry,
Inc., is an HNET module that interfaces
to a Centronics parallel printer. It must
be located where access to the
FireFinder-XLS/Desigo Fire Safety
Modular/Cerberus PRO Modular HNET
network and the PSC-12 24VDC power
limited output are available.
The RPM is required whenever a logging printer is needed. It translates
the HNET messages into a standard Centronics printer interface. When used
in conjunction with the PAL-1, it provides a supervised logging printer meeting the
requirements of NFPA 72 Proprietary or UL 1076 Security systems. For NFPA 72
Local, Auxiliary or Remote Station applications any UL EDP listed Centronics parallel
printer may be used (See notes 2, 3, and 4 on Figure 3).
The RPM also provides an optional Foreign System Interface (FSI). The FSI allows
other building systems to monitor the status of the FireFinder-XLS/Desigo Fire Safety
Modular/Cerberus PRO Modular system. The FSI connects to Ports 1-3 on the RPM.
This connection can be either RS-232 (Ports 1 or 3) or RS-485 (Port 2). Only one FSI
connection per RPM is allowed. The FireFinder-XLS/Desigo Fire Safety Modular/
Cerberus PRO Modular system supports a maximum of two simultaneous FSI
connections. With two simultaneous FSI connections the following combinations are
supported: Two Local FSI connections or one Global and one Local FSI connection. A
total of two Global FSI connections are supported in an XNET network. Each Global
FSI connection must originate from its own XLS/Desigo Fire Safety Modular/
Cerberus PRO Modular node.
Features RPM features are as follows:
Supervision of the PAL-1 includes paper out, paper jam, printer off line,
printer power off and printer disconnected.
Can be connected to the HNET either Style 4 or Style 7.
Includes diagnostic LEDs to indicate failure of the HNET or the CPU. It also
has a power on indicator.
Includes a reset switch in the event that the RPM requires a hardware
reset.
Can be mounted on any smooth surface within 6 feet of the PAL-1.
Single Foreign System Interface (FSI) connection.
FSI supports Local (single system) or Global (multiple systems) operation.
Figure 1
RPM Remote Printer Module
Remote Printer Module
Installation Instructions
Model RPM
Question and Answer IconNeed help?

Do you have a question about the Siemens RPM and is the answer not in the manual?

Siemens RPM Specifications

General IconGeneral
BrandSiemens
ModelRPM
CategoryControl Unit
LanguageEnglish

Summary

Introduction to the RPM Module

RPM Module Overview

Details the Siemens RPM as an HNET module for Centronics parallel printers.

RPM Module Features

RPM Connectivity and Interface

Covers HNET connection styles, FSI connections, and supervision features.

RPM Control and Indicators

Details diagnostic LEDs and the hardware reset switch for the RPM.

Module Operation

Event Handling and Buffering

Explains how the RPM handles system events and buffers messages.

Foreign System Interface (FSI) Operation

Describes how events are sent to the FSI port and managed.

HNET Side Panel Controls and Indicators

Reset Switch and Address Setting

Details the function of the reset switch and how to set the HNET address.

Module Status LEDs

Explains the Power, CPU Fail, and HNET Fail indicator LEDs.

Pre-Installation Configuration

Setting the HNET Network Address

Procedure for setting the RPM's HNET network address using a 3-position switch.

HNET Termination Switch

Guidance on setting the termination switch for Style 4 HNET networks.

Wiring and Power Connection

Power Connection Requirements

Specifies the 24VDC power requirements and connection methods for the RPM.

RPM in Middle of Style 4 HNET

Details wiring for the RPM when placed in the middle of a Style 4 HNET.

HNET Wiring Configurations

RPM in Middle of Style 7 HNET

Details wiring for the RPM when placed in the middle of a Style 7 HNET.

RPM at End of Style 4 HNET

Explains how to connect the RPM at the end of a Style 4 HNET network.

Power and FSI Connections

UPS Power Source Connection

Diagram and notes for connecting a UPS to the PAL-1 for standby power.

FSI RS-232 Connection Details

Specifies wiring for the RS-232 Foreign System Interface connection.

FSI RS-485 and Installation

FSI RS-485 Connection Details

Details wiring and notes for the RS-485 Foreign System Interface connection.

RPM Mounting Procedure

Instructions on selecting a surface and mounting the RPM unit securely.