Parameter Name Value Range
Factory
Setting
Your
Setting
Page
Number
Setpoint 1 SPL…SPH 60
Setpoint 2 SPL…SPH 0
Setpoint shift SPL…SPH 0
Analog input 1 N/A -
Angular positioning N/A -
Proportional band 1…9999 10
Derivative time 0…9999 sec 80
Integral time 0…9999 sec 350
Dead band 0.0…999.9 1
Controlling element running time 10…3000 sec 15
Switch-on threshold -1999…0.0 -5
Switch-off threshold (stage II) 0.0…HYS3 3
Switch-off threshold 0.0…9999 5
Switch-on threshold 0.0…9999 5
Switch-off threshold (stage II) HYS6…0.0 -3
Switch-off threshold -1999…0.0 -5
Response threshold 0.0…999.9 0 28
SEn1 Analog input 1 sensor type 1…19 → 1
OFF1 Analog input 1 correction (offset) -1999…9999 0
SCL1 Analog input 1 scale low level -1999…9999 0
SCH1 Analog input 1 scale high level -1999…9999 100
dF1 Analog input 1 filter time constant 0.0…100.0 sec 0.6
Unit Temperature units 1, 2 1
Controller type 1, 2 N/A
Operating action 0, 1 1
Setpoint low limit -1999...9999 0
Setpoint high limit -1999...9999 100
Lower working range limit -1999…9999 -1999
Upper working range limit -1999…9999 9999
Thermal shock function 0, 1, 2 0
Ramp slope 0.0…999.9 0
Tolerance band ramp 2*|HYS1|…9999 0
Ramp limit value 0…250 0
Analog output function 0, 1, 4 4
Analog output signal type 0, 1, 2 0
Value when input is out of range 0…101 % 0
Re-transmit scale low -1999…9999 0
Re-transmit scale high -1999…9999 100
binF Binary input 1 function 0, 1, 2, 4 0 46
Upper display 0, 1, 4, 6, 7 1
Lower display 0, 1, 4, 6, 7 6
Timeout 0…255 sec 180
Decimal places 0, 1, 2 0
Locking of levels 0, 1, 2, 3 0
44
45
47
34
RWF50 Menu Options
40
42
43
ConF
Cntr
rAFC
0utP
diSP
PArA
dt
HYS3
HYS4
HYS5
HYS6
rt
tt
HYS1
HYS2
Pb1
q
InP1lnP
FnCt
oLHi
FnCt
rASL
toLP
rAL
CtYP
CACt
SPL
SPH
oLLo
diSU
diSL
tout
dECP
SiGn
r0ut
0Pnt
End
bin1
Parameters Notes
Only if bin1 = 1
Cannot be edited here (just a display)
Opr
SP1
SP2
lnP1
Y
dSP
Only if bin1 = 2
Cannot be edited here (just a display)
RWF 50.2 only
1 = Pt-100 3-wire, 2 = Pt100 2-wire,
3 = Pt1000 3-wire, 4 = Pt1000 2-wire,
5 = Ni1000 3-wire, 6 = Ni1000 2-wire,
7 = 0-135 Ohm, 15 = 0-20 mA, 16 = 4-20 mA,
17 = DC 0-10 V,18 = DC 0-5 V, 19 = DC 1-5 V
RWF 50.2 only
Only if CACt = 1
Only if CACt = 1
Only if CACt = 1
Only if CACt = 0
0 = no function, 1 = analog input 1,
4 = controller angular position
1 = Celsius, 2 = Fahrenheit
0 = disconnected, 1 = Kelvin/min,
2 = Kelvin/hour
Only appears if FnCt ≠ 0
Only appears if FnCt ≠ 0
1 = 3-position (50.2 only),
2 = modulating (50.3 only)
0 = cooling controller, 1 = heating controller
0 = disconnected, 1 = analog input 1,
4 = controller angular position, 6 = setpoint,
7 = thermal shock end value
0 = no lockout, 1 = configuration level,
2 = parameter and configuration level,
3 = keyboard lockout
0 = no decimal place, 1 = one decimal,
2 = two decimals
Only if FnCt = 1
Only if FnCt = 1
0 = no function, 1 = setpoint changeover,
2 = setpoint shift,
4 = operating mode changeover
0 = disconnected, 1 = analog input 1,
4 = controller angular position, 6 = setpoint,
7 = thermal shock end value
0 = 0-20 mA, 1 = 4-20 mA, 2 = DC 0-10 V
Output percentage
Only appears if FnCt ≠ 0
CodE
Only if CACt = 0
Only if CACt = 0