Siemens Building Technologies SED2 variable speed drives CM1U5192en
HVAC Products Programming 01.2002
P2390
Hibernation frequency setpoint [%]
Setting range:
± 200 %
Recommended setting: Value 15 to 20% greater than the minimum frequency.
Note: The hibernation function is disabled if the hibernation setpoint is set to 0
(corresponds to the factory setting).
P2391
Hibernation timer [s]
Set the desired time T1 to T3 (before hibernation mode kicks in) (see diagram above).
Setting range: 0 to 254 s
P2392
Restart PID controller deviation [%]
This parameter defines the PID controller deviation at which the motor is to restart.
Setting range:
± 200 %
Note the signs according to the application (heating or cooling sequence).
Complete parameter setting by changing over to automatic control.
Parameterizing the
hibernation function
(commissioning)