Commissioning
6.4 Modbus address register for devices with Modbus interface
7KT multimeter
58 Manual, 08/2018, 2514284149-01
M03 Password
CODE
MENU
MIN
MAX
DEF
WORDS
ADDRESS
P03.01
Enable password
0
1
0
1
5100H
P03.02 User-level password 0 9999 1000 1 5102H
P03.03
Administrator password
0
9999
2000
1
5104H
M04 Integration
CODE
MENU
MIN
MAX
DEF
WORDS
ADDRESS
P04.01 Demand values 0 3 1 1 5180H
P04.02
Power demand values
1
60
15
1
5182H
P04.03 Current demand values 1 60 15 1 5184H
M05 Hour counter
CODE
MENU
MIN
MAX
DEF
WORDS
ADDRESS
P05.01 Activate total hour coun-
ter
0 1 1 1 5200H
P05.02 Activate partial hour
counter
0 4 1 1 5202H
M07 Communication
CODE
MENU
MIN
MAX
DEF
WORDS
ADDRESS
P07.n.01
Address
1
255
1
1
5300H + (n -1) x 80H
P07.n.02
Baud rate
0
5
3
1
5302H + (n -1) x 80H
P07.n.03
Data format.
0
4
0
1
5304H + (n -1) x 80H
P07.n.04
Stop bits
0
1
0
1
5306H + (n -1) x 80H
P07.n.05
Protocol
0
1
0
1
5308H + (n -1) x 80H