Commissioning
6.4 Modbus address register for devices with Modbus interface
7KT multimeter
Manual, 08/2018, 2514284149-01
59
Rules for reading and writing
Parameters are read and written in accordance with the following rules:
0x5000 1 Selection of menu number 4 read – 6 write Write the value 1 to select
0x5001 1 Selection of submenu num-
ber
Write the value 4 to select
submenu number 4. If the
number of the submenu is
0x5002 1 Selection of parameter num-
Write the value 2 to select
0x5004 1 … 28 Parameter value 4 read – 6 write
–