Indirect contact
Figure 3: Protection against indirect contact
R
st
R
m
I
M
R
B
3.3 Fire protection
DIN VDE 0100-482 requires measures for the prevention of  res which can be
caused by insulation faults in “locations exposed to  re hazards”. This stipulates
that cables and conductors in TN and TT systems must be protected by means of
residual current protective devices with a rated residual current of I
Δn
≤ 300 mA.
This does not include mineral-insulated cables and busbar systems.
In applications in which resistive faults can cause a  re (e.g. radiant ceiling heating
with panel heating elements), the rated residual current must be I
Δn
= 30 mA. The
re protection provided by residual current protective devices, however, should
not be limited to locations exposed to  re hazards but should always be provided.