The dimensioning of the SIQUENCE universal current-sensitive Type B RCCB‘s
frequency response takes these boundary conditions into account, and represents
a solid compromise between re protection and operational safety. Since the in-
uence of existing capacitive leakage currents on the tripping of the RCCB is clearly
limited, the RCCB can be used in a signicantly larger number of applications.
The use of Type B+ residual current protection devices is recommended if the use
of residual current protection devices with rated residual currents of max. 300 mA
is required in accordance with DIN VDE 0100-482 “Fire protection against special
risks or hazards” in connection with DIN VDE 0100-530. They meet all requirement
of the well-known Type B, but remain below the tripping value of 420 mA at up
to 20 kHz in accordance with product standards DIN VDE 0664-400 (RCCBs) and
DIN VDE 0664-401 (RCBOs) as well as VdS Guideline 3501, thus offering an in-
creased level of preventive re protection.
High-intensity leakage currents can occur briey when capacitors connected to
the PE protective conductor are switched on (e.g. in the case of EMC lters in
conjunction with frequency converters). In order to ensure trouble-free operation
in such cases, the SIQUENCE universal current-sensitive Type B and Type B+ RCCBs
are always super-resistant and feature short-time delayed tripping (Type
K
).
Residual current protective devices