Fault locations in section 1 (upstream of the FC)
Line-frequency AC residual currents occur between the RCCB and the frequency
converter (see gure 18). Protection against these purely sinusoidal 50 Hz residual
currents is provided by all RCCBs (types AC, A, F and B). The section at risk is dis-
connected when the tripping value in the range 0.5 to I
Δn
is reached.
Fault locations in section 2 (in the FC)
Practically smooth DC residual currents occur in the frequency converter (be-
tween the input rectier and the output electronics, i.e. in the DC link circuit)
(see gure 19). There is reliable disconnection in the range from 0.5 to 2 2 I
Δn
if a Type B universal current-sensitive RCCB is used.
Notes on installation and use
Figure 18: Residual current waveform at fault location 1
Figure 19: Residual current waveform at fault location 2