A.4 Installation standards for electrical installations with residual current
protective devices
Standard
(DIN VDE ...
or BGI ...)
Application Required
I
Δn
[mA]
Recommended Siemens RCCB
(taking into consideration possible
nature of the residual currents in
the equipment)
Type
A
Type
F
SIQUENCE
Type B/ B+
SIGRES
0100-410 Protection against electric
shock
30 ... 500 + + + +
Socket outlets up to 20 A,
outdoor installations
10 ... 30 + +
0100-482 Fire protection for
particular risks or safety
hazards
30 and 300 + + +
0100-701 Rooms with baths or
showers, socket outlets
in zone 3
10 ... 30 + +
0100-702 Pools in swimming baths
and other pools
10 ... 30 + +
0100-703 Rooms and cabins with
sauna heating systems
10 ... 30 + +
0100-704
und
BGI 608
Construction sites, socket
outlet circuits up to 32 A
and for hand-held tools,
plugs and sockets
I
n
> 32 A
≤ 30 mA
≤ 500 mA
+
+
+
+
+
+
+
+
0100-705 Agricultural and
horticultural, general,
socket outlet circuits
≤ 300
10 ... 30
+
+
+
+
+
+
0100-706 Conductive areas with
limited freedom of
movement, fixed equip-
ment
10 ... 30 +
0100-708 Electrical installations on
camping sites, each socket
outlet individually and
each branch circuit for a
fixed connection to the
supply
10 ... 30 + +