System Messages
C-8
TP 170A Equipment Manual
Release 12/99
RemedyEffect/CauseNumber
140008 No tag updating or writing is executed
because the configuration data is incorrect:
The following parameters could not be
entered in the registry:
0: General errors
1: Incorrect version
2: Profile cannot be entered in the registry.
3: Sub-network type cannot be entered in
the registry.
4: Target rotation time cannot be entered
in the registry.
5: Highest address (HSA) incorrect.
Check the connection and whether the PLC
is switched on.
Check the parameter definitions in the
Control Panel using “Set PU/PC interface”.
Restart the system.
140009 No tag updating or writing is executed
because the module for the S7
communication was not found.
Re-install the module in the Control Panel
using “Set PU/PC interface”.
140010 No S7 communication peer could be found
because the PLC is switched off.
DP/T:
The option “Is not active as the only master”
is set in the Control Panel under “Set PU/PC
interface”.
Switch the PLC on.
DP/T:
If only one master is connected to the
network, deactivate the option “Is not active
as the only master” in “Set PU/PC interface”.
If the network has more than one master,
switch this master on. Do not modify any
settings here, otherwise a bus fault may
occur.
140011 No tag updating or writing is executed
because communication is interrupted.
Check the connection and that the
communication peer is switched on.
140012 There is an initialization problem (e.g. when
ProTool/Pro RT has been terminated in the
Task Manager).
Or: another application (e.g. STEP7, WINCC)
is active with different bus parameters and
the driver cannot be started with the new bus
parameters (e.g. baud rate).
Restart the operating unit.
Or start ProTool/Pro RT first and then the
other applications.
140013 The MPI cable is not plugged in and, thus,
there is no power supply.
Check the connections.
140014 – Modify the operating unit address in the
configuration in
PLC
.
140015 Incorrect baud rate
Or: incorrect bus parameter (e.g. HSA)
Or: OP address HSA
Or: incorrect interrupt vector (interrupt does
not arrive at the driver)
Correct the incorrect parameters.
140016 – Change the interrupt number.
140017 – Change the interrupt number.