System Messages
C-9
TP 170A Equipment Manual
Release 12/99
RemedyEffect/CauseNumber
150000 No more data is read or written.
This can have various causes:
S The cable is defective.
S The PLC does not respond, is defective,
etc.
S Connection made to the wrong interface.
S The system is overloaded.
Check that the cable is plugged in, the PLC
is operational, the correct interface is used.
Reboot the system if the system message is
displayed continuously.
150001 Connection is re-established because the
cause of the interruption has been
eliminated.
–
160000 No more data is read or written.
This can have various causes:
S The cable is defective.
S The PLC does not respond, is defective,
etc.
S Connection made to the wrong interface.
S The system is overloaded.
Check that the cable is plugged in, the PLC
is operational, the correct interface is used.
Reboot the system if the system message is
displayed continuously.
160001 Connection is re-established because the
cause of the interruption has been
eliminated.
–
160010 There is no connection to the server
because the server identification (CLS-ID)
cannot be established.
Values cannot be read or written.
Check the access rights.
160011 There is no connection to the server
because the server identification (CLS-ID)
cannot be established.
Values cannot be read or written.
Check, for example, whether:
S the server name is correct
S the computer name is correct
S the server is registered
160012 There is no connection to the server
because the server identification (CLS-ID)
cannot be established.
Values cannot be read or written.
Check, for example, whether:
S the server name is correct
S the computer name is correct
S the server is registered
Information for experienced users:
Interpret the value from HRESULT.
170000
1)
S7 diagnostics messages are not displayed
because it is not possible to logon to the S7
diagnostics with this unit. The service
program is not supported.
–
170001
1)
The S7 diagnostics buffer cannot be
displayed because communication with the
PLC has been switched off.
Switch the PLC
online
170002
1)
The S7 diagnostics buffer cannot be
displayed because reading in the diagnostics
buffer (SZL) was terminated due to an error.
–